SiBE04-624 Troubleshooting
Service Diagnosis 151
2.8 Peak-cut Control or Freeze-up Protection
Remote
Controller Display
A5
Method of
Malfunction
Detection
Peak-cut control (high pressure control)
During heating operation, the temperature detected by the indoor heat exchanger thermistor
is used for the high pressure control (stop, outdoor fan stop, etc.).
Freeze-up protection control (operation halt) is activated during cooling operation according
to the temperature detected by the indoor heat exchanger thermistor.
Malfunction
Decision
Conditions
Peak-cut control
On heating operation, when indoor heat exchanger temperature is about 65°C or more
Freeze-up protection
On cooling operation, indoor heat exchanger temperature is 0°C or less
Supposed
Causes
Halt due to dirty indoor unit filter
Halt due to dirty indoor heat exchanger
Halt due to short circuit
Faulty detection due to defective indoor heat exchanger thermistor
Reheating dehumidification solenoid valve remains closed (on cooling operation)
Faulty detection due to defective indoor unit PCB