SiBE04-624 Troubleshooting
Service Diagnosis 149
Troubleshooting
Correct it within the
specified length.
Explain it to the user.
Reset the hose length by
remote controller.
Clean the humidification
filter.
Repair breakage or remove
blockage.
Explain to the user to use
the proper hose specified
by DAIKIN.
Improve so as not to get
short-circuit.
Explain to the user.
Explain to the user.
Explain to the user.
Explain to the user.
Explain to the user to set
the air outlet at the height
of 1.8 m. Confirm the
humidification performance.
Does
the length of humidification
hose exceed the specified
length?
(R6000)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Does the
set hose length match with
the field hose
length?
Is the humidification filter
blocked?
Blocked.
NO
It does not match.
Exceeds.
YES
Under specified length.
It matches.
Not blocked.
YES
NO
Any breakage
or blockage on humidification
hose?
Is the
humidification hose
proper?
Does the
outdoor unit suck the
exhausted air again by
short-circuit?
YES
How
many times are the room
ventilated?
Is the
ceiling too high for
the floor size?
High (wellhole, high ceiling)
Low
Many (screens, consecutives room )
High
NO
Small in number(highly packed house or apartments)
NO
Not low
NO
Is the
set temperature by remote
controller too high?
Is the
outdoor temperature or
humidity extremely
low?