OTHER CONFIGURATION PARAMETERS
If the installation has Auxiliary Heat, verify that it is correctly
installed and configured. Verify that the Operation Mode
menu displays Emergency Heat as an option.
If you use Auxiliary Heat, check the relay operation in the
zoning box control board to ensure it is working properly
(first Aux H1, then Aux H2). To verify, set the system calling
demand for heat and keep in mind that there is an action
delay.
Turn off the system and verify that Aux H1 and Aux H2 are
disabled.
Meaning
Aux. Heat
status
Normal
status
Color
D6 1st Stage Auxiliary heat
On
On
Green
Off
Off
D7 2nd Stage Auxiliary heat
On
On
Green
Off
Off