Series Installation Manual
Table Of Contents
- Warnings, environmental policy, and certifications
- System description
- Description, installation and connection of the components
- Initial configuration
- Advanced configuration
- User settings – Wired Thermostat
- Zone settings
- Commissioning steps
- Exception codes
- Auto diagnostics
- Navigation guide
- Troubleshooting
- Wiring diagram
- Página en blanco
31
Installation Manual
Rev. 2.00 Date 01-2019
Note: in case of system reset, it will
return to default values.
Note: the Remote Assistance
parameter enables a qualified
technician the remote access to
your installation in order to
perform a diagnose of it.
Autochange. This option allows the user to configure the three
values that define the auto-changeover operation that sets the
mode of the indoor unit.
- Setpoint Differential. Defines the minimum differential
between heating and cooling set points. For example, if set
to 2˚F, the system will force the cooling set point at least two
degrees higher than the heating set point. Values: 0 to 7˚F /
0 to 3.5˚C in increments of 1˚F / 0.5˚C, by default 2˚F / 1˚C.
- Mode Switching Protection (min). Defines the minimum
run time before allowing a mode change. Possible values are
15, 30, 60 and 90 minutes. By default, 30 minutes.
- Heat OVR Temp. If a zone has a higher heating demand than
this temperature, the system reverts heating operation even
if the cooling global demand exceeds the global heat
demand. Possible values are: Off, 3 to 8˚F / 1.5 to 4˚C in
increments of 1˚F / 0.5˚C. Default value: Off.
BACnet. This parameter displays the Device ID, the uplink port, the
IP address, the subnet mask and the Gateway IP and allows you to
modify them. Press on the value you want to change, modify it and
then press to confirm. The values by default are:
- Port: 47808
- IP Address: 192.168.0.100
- Subnet Mask: 255.255.255.0
- Gateway IP: 192.168.0.1
Room Temperature. This option allows the room temperature and
relative humidity to be shown/hidden. By default, the room
temperature is shown.
Lite Step. This option configures the temperature increments
(2˚F/1˚C or 1˚F/ 0.5˚C) of the base set-point for the Wireless Lite
Thermostat. By default, 1˚F/0.5˚C.
Remote Assistance. This option enables/disables remote
assistance. By default, remote assistance is disabled.
Reset System (only available for the Main thermostat). This option
resets the system and returns to factory settings.