Series Installation Manual

Table Of Contents
28
Installation Manual
Rev. 2.00 Date 01-2019
Note: when global ventilation is
activated, a warning message will
appear on the screensaver.
ADVANCED CONFIGURATION
Besides the quick configuration menu, the system has a number of
configuration parameters to complete the installation.
ADVANCED CONFIGURATION - WIRED THERMOSTAT
To access the advanced configuration menu, follow the next steps:
From this menu you can change the system and zone parameters.
System Parameters
System ID. This option allows the installer to define the number of
this DZK system within the whole installation. By default, the value
is 1. The system displays the available IDs with a maximum value of
16.
Note: If you have a DZK BACnet Interface, this parameter is not
displayed and the address of the system is 1.
Temperature SP Range. This menu allows you to change the
maximum set point temperature for heating mode (66˚F to 86˚F /
18˚C to 30˚C, by default 86˚F/30˚C) and minimum set point
temperature in cooling mode (64˚F to 78˚F / 18˚C to 26˚C, by default
64˚F/18˚C).
Global Ventilation. This menu allows you to activate/deactivate
the fan mode in all zones when the system is not actively heating or
cooling any zones. By default, the global ventilation is deactivated.
When activated, the following settings are used to configure Global
Ventilation:
Every (min). Configure the length of the interval (in minutes)
between periods of ventilation. Configurable from 5 to 40
minutes, in 5 minutes increments (by default, 15 minutes).
Press and hold