Series Installation Manual

Table Of Contents
23
Installation Manual
Rev. 2.00 Date 01-2019
Important: perform the pairing of
thermostat in their final location.
Distances less than 18 inches
between the thermostat and the
control board can saturate the
receivers and make the pairing
impossible.
WIRED THERMOSTAT
Installation
The Wired Thermostat is available for wall mount. The wiring should
not exceed 130 ft. (40 m) and stranded AWG20 shielded cable
should be used. To mount the thermostat on the wall, take the
following steps:
Separate the back part of the thermostat from the wall
support and make all the connections.
Fix the back part of the thermostat to the wall.
Place the display on the support once it is fixed.
Wiring
The Wired Thermostats are connected to the DZK connection bus of
the DZK Control Board. Attach the wires with the terminal screws
following the color code.
Important: Use a suitable screwdriver to press in the locking tabs.
WIRELESS AND WIRELESS LITE THERMOSTAT
Installation
The Wireless and Wireless Lite Thermostats are available for wall
mount. The maximum distance between the Zoning box control
board and the thermostat in clear line of sight is 130 ft. (40 m). To
mount the thermostat on the wall, take the following steps:
Remove the back of the thermostat and insert the CR2450
button battery.
Fix the back part of the thermostat to the wall.
Place the display on the support once it is fixed.