Series Installation Manual

Table Of Contents
12
Installation Manual
Rev. 2.00 Date 01-2019
DESCRIPTION, INSTALLATION AND
CONNECTION OF THE COMPONENTS
GENERAL RECOMMENDATIONS
Closely follow the instructions on this manual to avoid installation
and maintenance issues.
The system should only be installed by qualified personnel.
Never use solid wire to install the system. This is a
communication device and requires the use of
communication cables.
While connecting the devices, be sure the system is not
powered.
Follow the local installation regulations for low and high
voltage installation.
The recommended specifications for the cable to install this
system are: 4 wires, stranded, AWG 20, plenum and shielded.
When connecting to other systems fed with high voltage,
only use the A and B contacts of the communication bus. It is
not recommended to connect the + and contacts, nor the
ground.
Follow the color codes and polarity indications in the system
components.
Do not run the bus cable near high power cables or near
electrical motors to avoid electromagnetic interference in
the system communications.
Use the following recommendations to locate the
thermostats:
The temperature operating range is: 32 to 122˚F (0 to 50˚C).
The humidity operating range is: 5 to 90% (non-condensing).
h= 5 ft