Brochure
2019
PF-DZKBAC3 06-19
Typical Zoning Kit
Configuration —
4 Zones
DZK KIT STRUCTURE AND GENERAL TECHNICAL DATA
DZK Product Number DZK030E4-3 DZK030E5-3 DZK048E4-3 DZK048E6-3 DZKS015E3-3 DZKS015E4-3 DZKS030E4-3 DZKS030E5-3 DZKS048E4-3 DZKS048E6-3
KIT STRUCTURE
Number of Zones
Compatibility
Up to 4 Up to 5 Up to 4 Up to 6 Up to 3 Up to 4 Up to 4 Up to 5
Up to 4 Up to 6
Number of Air Duct
Outlets x Diameter (")
4 x Ø8" 5 x Ø6" 4 x Ø8" 6 x Ø6" 3 x Ø8" 4 x Ø6" 4 x Ø8" 5 x Ø6" 4 x Ø8" 6 x Ø6"
TECHNICAL DATA
Height (")
10.44 10.25 10.44 10.25 9.63 9.31 9.63 9.31 9.63 9.31
Width (") 43.58 53.46 34.19 43.63 53.44
Depth (") 10.43
Weight (lbs) 18 20 23 16 18 18 20 18 23
Input Voltage 110/230 VAC
Full Load Amps (A) 0.25
UNIT COMPATIBILITY
FXMQ15-24PBVJU
■ ■
FXMQ30-54PBVJU
■ ■
FBQ18-30PVJU
■ ■
FBQ36-42PVJU
■ ■
FXSQ15TAVJU
■ ■
FXSQ18-30TAVJU
■ ■
FXSQ36-48TAVJU
■ ■
FDMQ09-12RVJU
■ ■
FDMQ15-24RVJU
■ ■
ZONING BOX
INDOOR UNIT
FAN COIL
(FXMQ-P OR FBQ-P)
NAVIGATION
REMOTE
CONTROLLER
WIRELESS
THERMOSTATS
WIRED
THERMOSTAT
ZONING BOX
CONTROL BOX
P1
P2
DAIKIN ZONING KIT
WIRELESS
THERMOSTAT
WIRED
THE RMOSTAT
DZK BACNET
®
POINTS
Common Points
DZK System Alarm DZK Aux Heat2 DZK Error
DZK Global Fan
DZK/BACnet board
Communication Error
DZK Operation Mode
DZK Aux Heat1
Zone Points
(per zone)
ON/OFF Unoccupied Cooling Demand
Local Ventilation Room Temperature Heating Demand
Vacation Override Heating Setpoint Aux Heating Demand
Room Humidity Cooling Setpoint Opening Step Damper
Indoor Unit Points
IU Status ON/OFF IU Errors DZK Address (DK airnet address)
IU Speed IU Set Point DZK Group Address (DK group address)