Specifications

EDUS391000-C Control Devices
Controls 53
4. Forced reset switch (SS1)
When changing the setting of the connector for individual use, etc., the switch can be reset simply by setting it to the
reset side once and returning to the normal side. This procedure enables to reset without turning off the power. (Set
the normal side at normal operation.)
5. Setting for special function
When you want to have a programmed operation of a part of indoor units by using only schedule timer, cut off JP1
and supply the power again.
You can have a programmed operation of the indoor units set the address for central control by local remote controller.
3. Transmission Wiring
In case of individual use of schedule timer
Connect terminals of the schedule timer (F1, F2) with terminals of the indoor unit (F1, F2). Connect terminals of the schedule
timer (D1, D2) and the connector on the indoor unit PC board, using the attached electric wire and crimp style terminals.
Prevent the connection part of crimp style terminal from getting out of the electric parts box of indoor unit.
In case of combined use with other optional controllers for centralized control
Connect terminals of the schedule timer (F1, F2, D1, D2) and the terminals of the central remote controller (or unified
ON/OFF controller).