Specifications

EDUS391000-C Control Devices
Controls 37
6. Refreshed operation
Refreshed operation is the function to transmit setting of "Temperature control", "Temperature setting" automatically
from DCS302C71.
"Refreshed operation" is "ON" when shipped from the factory.
Factory Setting
It depends on the setting of outdoor systems that an indoor unit setting is "Temperature control " or " Temperature
setting".
In case of Refreshed operation is "ON"
When setting is changed by DCS302C71, it operates by this setting from the next operation.
If it sets up with 79°F in cooling by DCS302C71, next operation will also be operated at 79°F in cooling. (Even if it has
changed into heating operation, fan only operation with wired or wireless remote control, it operates at 79°F in
cooling.)
When zone registration is carried out by Central Remote Controller.
It operates from next time with the value set up in the zone.
When a zone 1 is set up with 68°F of heating. (Refer to the system of the following figure.)
When controlled by Central Remote Controller, 3 indoor units registered into the zone 1 are operated by 68°F of
heating. Because priority is given to zone setting, even if it sets up 2-02 with 77°F of heating on an individual screen
from Central Remote Controller, 2-02 is operated at 68°F.
When there are two or more indoor units in a zone.
Because an operating mode depends on the outdoor unit, the operating mode of each indoor unit does not become
the same setting.
When the outdoor unit system 1 is cooling, the outdoor unit system 2 is heating and it operates by the system of the
following figure. Setting of a zone 2 is operated in heating mode, because 2-03, 2-04, and 2-05 do not have a cooling/
heating selection right as for 79°F of cooling, but temperature setting becomes 79°F.
When you unify the operating mode of an indoor unit in the same zone, please set up a zone in the indoor unit of the
same outdoor unit system.
Outdoor Units Systems Indoor Units Mode
Cooling Mode Cooling 82°F
Heating Mode Heating 72°F
Fan Mode Fan Operation
Outdoor Unit
System 1
Outdoor Unit
System 2
Cooling/Heating Selection Right
1-00 1-01 1-02 1-03 1-04 1-05
Zone 2
2-00 2-01 2-02
Zone 1
2-03 2-04 2-05
Central Remote
Controller