Specifications
ED01-505 Installation Manual
Room Air Conditioners D-Series 27
4
WIRING
5
DRAIN PIPING
•
Connect the drain hose, as described below.
•
When drain hose requires extension, obtain
an extension hose commercially available.
Be sure to thermally insulate the indoor
section of the extension hose.
•
When connecting a rigid polyvinyl chloride pipe (nominal diameter 13mm) directly to the drain
hose attached to the indoor unit as with embedded piping work, use any commercially available
drain socket (nominal diameter 13mm) as a joint.
Indoor unit
drain hose
Extension drain hose
Heat insulation tube
(Field supply)
Drain hose supplied with
the indoor unit
Commercially available
drain socket
(nominal diameter 13mm)
Commercially available rigid
polyvinyl chloride pipe
(nominal diameter 13mm)
The drain hose should
be inclined downward.
No trap is permitted.
Do not put the end
of the hose in water.
•
Remove the air filters and pour some
water into the drain pan to check
the water flows smoothly.
1) Strip wire ends (15mm).
2) Match wire colours with
terminal numbers on indoor
and outdoor unit’s terminal
blocks and firmly screw wires
to the corresponding terminals.
3) Connect the earth wires to the
corresponding terminals.
Attach the earth wire so that it is not connected to the fan motor
connector.
4) Pull wires to make sure that they are securely latched up, then retain
wires with wire retainer.
5) In case of connecting to an adapter system.
Run the remote controller cable and attach the
S21 connector as the illustration right.
6) Shape the wires so that the service lid fits
securely, then close service lid.
Shape wires so
that the service
lid will fit securely.
Terminal block
Electrical component box
Wire retainer
Firmly secure wire retainer
so that wires sustain no
external stress.
Use the
specified
wire type.
Connector for fan motor
1
2
3
123 LN
Safety
breaker
15A
Earth leakage
circuit breaker
Earth
When wire length exceeds
10m, use 2.0-mm wires.
H05VV
Firmly fix the wires with
the terminal screws.
Outdoor unit
Indoor
unit
Power
supply
50Hz 230V
Firmly fix the wires with
the terminal screws.
1) Do not use tapped wires, stand wires, extensioncords, or starbust
connections, as they may cause overtheating, electrical shock,or fire.
2) Do not use locally purchased electrical parts inside the product. (Do not
branch the power for the drain pump, etc., from the terminal block.) Doing
so may cause electric shock or fire.
Warning
φ18
PCB
S21