Specifications

ED01-505 Installation Manual
Room Air Conditioners D-Series 25
Indoor Unit
BORING A WALL HOLE AND INSTALLING WALL EMBEDDED PIPE
2
1
For walls containing metal frame or metal board, be sure to use a wall embedded pipe and
wall cover in the feed-through hole to prevent possible heat, electrical shock, or fire.
Be sure to caulk the gaps around the pipes with caulking
material to prevent water leakage.
(1) Bore a feed-through hole of 65mm in the wall so
it has a down slope toward the outside.
(2) Insert a wall pipe into the hole.
(3) Insert a wall cover into wall pipe.
(4) After completing refrigerant piping, wiring, and drain
piping, caulk pipe hole gap with putty.
Inside Outside
Caulking
Wall embedded pipe
(field supply)
Wall hole cover
(field supply)
Wall embedded pipe
(field supply)
INSTALLING THE MOUNTING PLATE
The mounting plate should be installed on a wall which can support the weight of the indoor unit.
(1) Temporarily secure the mounting plate to the wall, make sure that the panel is completely
level, and mark the boring points on the wall.
(2) Secure the mounting plate to the wall with screws.
Recommended mounting-plate retention spots and Dimensions
φ
65
80
100
400
135
450
283
47.5
141.5
50.5
46.5
44.5
131.5
87
44.5
110
60 130
220 50
60 110
800
φ65 φ65
Use tape
measure
as shown.
Position the
end of a tape
measure at
Keep here the piece cut out
from the unit for piping.
Gas pipe end
Liquid pipe end
* The removed pipe port cover can be
kept in the mounting plate pocket.
Removed pipe
port cover.
A
Mounting plate
Through-
the-wall
hole 65mm
Drain hose
position
Recommended
mounting - plate
retention spots
(6 spots in all)
(Bolt size : M10)
Place a leveler
on raised tab.
(Bolt size : M10)