Specifications

ED01-505 Capacity Tables
Room Air Conditioners D-Series 15
FT35DVM+R35DV1
3D049931
Cooling (220V 50Hz)
AFR 9.9
BF 0.24
INDOOR
TEMP
OUTDOOR TEMPERATURE(°CDB)
20 25 30 32 35 40
EWB EDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
°C °C kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
14.0 20 3.672.580.863.502.500.943.332.411.023.272.371.063.172.321.113.002.241.19
16.0 22 3.832.540.863.672.460.953.502.371.033.432.341.063.332.291.113.172.211.20
18.0 25 4.002.640.873.832.560.953.662.481.033.602.451.073.502.411.123.332.331.20
19.0 27 4.08 2.76 0.87 3.91 2.68 0.95 3.75 2.61 1.04 3.68 2.58 1.07
3.58 2.54 1.12 3.41 2.47 1.20
22.0 30 4.332.650.884.162.590.963.992.521.043.932.491.083.832.461.133.662.391.21
24.0 32 4.492.580.884.332.510.974.162.451.054.092.431.083.992.401.133.832.341.22
Cooling (240V 50Hz)
AFR 9.9
BF 0.24
INDOOR
TEMP
OUTDOOR TEMPERATURE(°CDB)
20 25 30 32 35 40
EWB EDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
°C °C kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
14.0 20 3.672.580.913.502.501.003.332.411.093.272.371.123.172.321.183.002.241.26
16.0 22 3.832.540.923.672.461.013.502.371.093.432.341.133.332.291.183.172.211.27
18.0 25 4.002.640.923.832.561.013.662.481.103.602.451.133.502.411.193.332.331.28
19.0 27 4.08 2.76 0.93 3.91 2.68 1.01 3.75 2.61 1.10 3.68 2.58 1.14
3.58 2.54 1.19 3.41 2.47 1.28
22.0 30 4.332.650.934.162.591.023.992.521.113.932.491.153.832.461.203.662.391.29
24.0 32 4.492.580.944.332.511.034.162.451.124.092.431.153.992.401.203.832.341.29
Symbols NOTES:
AFR : Air flow rate (m³/min.) 1. Ratings shown are net capacities which include a deduction for indoor fan
motor heat.
2. shows nominal(rated) capacities and power input.
3. TC, PI and SHC must be calculated by interpolation using the figures in
the above tables. (Figures out of the tables should not be used for
calculation.)
4. SHC is based on each EWB and EDB.
SHC=SHC correction for other dry bulb.
=0.02×AFR(m³/min.)×(1–BF)×(DB–EDB)
Add SHCto SHC.
5. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 5m
Level difference : 0m
6. Air flow rate (AFR) and bypass factor (BF) are tabulated above.
BF : Bypass factor
EWB : Entering wet bulb temp. (°C)
EDB : Entering dry bulb temp. (°C)
TC : Total capacity (kW)
SHC : Sensible heat capacity (kW)
PI : Power input (kW)