Installation manual
5 ■English
Indoor Unit Installation
1. Installing the mounting plate
•Themountingplateshouldbeinstalledonawallwhichcansupporttheweightoftheindoorunit.
1)Temporarilysecurethemountingplatetothewall,makesurethatthepaneliscompletelylevel,andmarktheboring
pointsonthewall.
2)Securethemountingplatetothewallwithscrews.
Recommended mounting plate retention spots and dimensions
780
Use tape measure
as shown.
Keep here the piece cut out
from the unit for piping
unit: mm
Gas pipe end
Removed pipe
port cover
Recommended mounting plate
retention spots (5 spots in all)
Place a leveler
on raised tab.
59
330.5
241.747.3
160
59.5
50160
241.7
47.3
106
125.5
331
203
247
Drain hose position
Liquid pipe end
A Mounting plate
* The removed pipe port cover can be
kept in the mounting plate pocket.
Position the end of
a tape measure at .
Through-
the-wall
hole ϕ65mm
2. Boring a wall hole and installing wall embedded pipe
•Forwallscontainingmetalframeormetalboard,besuretouseawall
embeddedpipeandwallcoverinthefeed-throughholetopreventpossible
heat,electricalshock,orre.
•Besuretocaulkthegapsaroundthepipeswithcaulkingmaterialtoprevent
waterleakage.
1)
Boreafeed-throughholeof65mminthewallsoithasadownslopetowardtheoutside.
2)Insertawallpipeintothehole.
3)Insertawallcoverintowallpipe.
4)Aftercompletingrefrigerantpiping,wiring,anddrainpiping,caulkpipe
holegapwithputty.
Inside Outside
Caulking
Wall embedded pipe
(field supply)
Wall hole cover
(field supply)
Wall embedded pipe
(field supply)
ϕ65
3. Installing indoor unit
•Inthecaseofbendingorcuringrefrigerantpipes,keepthefollowing
precautionsinmind.
Abnormalsoundmaybegeneratedifimproperworkisconducted.
1)Donotstronglypresstherefrigerantpipesontothebottomframe.
2)Donotstronglypresstherefrigerantpipesonthefrontgrille,either.
1)
2)