Installation manual

English 12
7-2 EXAMPLE FOR THE WHOLE SYSTEM
7-3 POWER CIRCUIT, SAFETY DEVICE AND CABLE REQUIREMENTS
A power circuit (Refer to Table 3) must be provided for connection of the unit. This circuit must be protected
with the required safety devices, i.e. a main switch, a slow blow fuse on each phase and an earth leakage
circuit breaker.
When using residual current operated circuit breakers, be sure to use a high-speed type (0.1 second or
less) 30mA rated residual operating current.
Use copper conductors only.
Use insulated wire for the power cord.
Select the power supply cable type and size in accordance with relevant local and national regulations.
Use vinyl cord with sheath or cable (2 wire) of AWG 18-16 for transmission wiring.
Table 3
MCA: Min. Circuit Amps (A); MFA: Max. Fuse Amps (A)
NOTES
The above Table 3 of Electrical Characteristics refers to one BS unit.
See the Engineering data book for other details.
7-4 WIRING EXAMPLE
Here is shown a wiring example for one system transmission wiring.
Connect terminals F1 and F2 (TO IN/D UNIT) on the control PCB (A1P) in the outside unit EL. COMPO.
BOX and terminals F1 and F2 (TO OUT/D UNIT) of the control PCB (A1P) of the first BS unit A.
Units Power supply
Model Type Hz Voltage Min. Max. MCA MFA
BSVQ36P
BSVQ60P
VJ 60 208~230 187 253 0.1 15
Power supply wiring
Transmission wiring
Switch
Fuse
Outside unit
Power supply
Power supply
Main switch
Main switch
BS unit
Indoor unit
Remote controller
Cooling/Heating selectable indoor unit
Cooling-dedicated
indoor unit