Sound level is measured at 1.5m below the center of the body. 
Air flow rate can be changed over to Low mode or High mode.
Sound level is measured in an anechoic chamber.
Sound level generally become greater than this value depending on the operating conditions, reflected sound, and peripheral noise.
The sound level at the air discharge port is about 8 dB higher than the unit's sound level.
Even when the outdoor temperature is below -15°C, the system is operable down to -20°C with the preheater installed at the outdoor air intake side.
Models
VAM150FAVE VAM250FAVE VAM350FAVE VAM500FAVE
Temp. Exchange 
Efficiency (%)
[50Hz/60Hz]
Ultra-High
High
79/80 77/77
74/74 72/72
74/74 72/72
75/75 74/74
75/75 74/74
74/74 74/74
74/74 74/74
75/75 75/75
75/75 75/75
75/75
75/75
80/81 77/78.5
For Heating
Enthalpy
Exchange
Efficiency (%)
[50Hz/60Hz]
For Cooling
Low
64/64 64/64 65/65 62/62
Ultra-High
64/64 64/64 65/65 62/62High
69/71 68/69 70/71 67/68.5Low
58/58 58/58 61/61 58/58
Ultra-High
58/58 58/58 61/61 58/58High
64/66 62/63 67/68 63/65.5Low
Heat
Exchange
Mode
Sound Level
dB(A)
[50Hz/60Hz]
Bypass
Mode
27-28.5/28.5 28-29/29.5 32-34/34.5 33-34.5/34
Ultra-High
26-27.5/26.5 26-27/26 31.5-33/32 31.5-33/31High
20.5-21.5/19 21-22/19.5 23.5-26/22 24.5-26.5/24Low
27-28.5/28 28-29/29 32-34/34.5 33.5-34.5/35
Ultra-High
26.5-27.5/27 27-28/27 31-32.5/33 32.5-33.5/33High
20.5-21.5/20
Galvanized steel plate
21-22/20.5 24.5-26.5/22 25.5-27.5/24Low
150/150 250/250 350/350 500/500
Ultra-High
150/150 250/250 350/350 500/500High
110/110 155/145 230/210 350/300Low
269
X
760
X
509 285
X
812
X
800mm
24 33kg
Casing
VE: 1 phase, 220-240V/220V, 50Hz/60HzPower Supply
Self-extinguishable polyurethane foamInsulation Material
Air to air cross flow total heat (Sensible heat+ latent heat) exchangeHeat Exchange System
Specially processed nonflammable paperHeat Exchange Element Material
Multidirectional fibrous fleecesAir Filter
Sirroco fanType
Fan
Dimensions (H
X
W
X
D)
Weight
0.030
X
2 0.090
X
2kW
100 150 200mm
-15°C to +50°CDB, 80% RH or lessUnit ambient condition
Motor Output
Connection Duct Diameter
Air Flow Rate (m
3
/h)
[50Hz/60Hz]
69/98 64/98 98/142 98/147
Ultra-High
39/54 39/54 70/85 54/54High
20/24 20/20 25/15 25/20Low
External Static
Pressure (Pa)
[50Hz/60Hz]
VAM650FAVE VAM800FAVE VAM1000FAVEVAM1500FAVE
77/78 76/76 76.5/78 78/78
63/63 65/65 66/66 66/66
63/63 65/65 66/66 66/66
66/68 67/68 68/71 68/68
58/58 60/60 61/61 61/61
58/58 60/60 61/61 61/61
63/65 62/63 63/66 64/64
34.5-35.5/36 36-37/37 36-37/37
39.5-41.5/40.5
33-34/33 34.5-36/35 35-36/35 38-39/38
27-28/27 31-32/30 31-32/30 34-36/33
34.5-35.5/35.5
36-37/37 36-37/37
40.5-41.5/40.5
34-35/34 34.5-36/35 35.5-36/35 38-39/38
27-28.5/27 31-33/31 31-32/31 33.5-36/33
650/650 800/800 1,000/1,000 1,500/1,500
650/650 800/800 1,000/1,000 1,500/1,500
500/440 670/660 870/800 1,200/1,200
348
X
988
X
852
348
X
988
X
1,140 710
X
1,498
X
852
710
X
1,498
X
1,140
48 61 132
0.140
X
2 0.230
X
2 0.230
X
4
250 350
93/162 137/225 157/196 137/206
39/69 98/118 98/108 98/118
25/34 49/69 78/69 49/69
VAM2000FAVE
78/78
66/66
66/66
70/70
61/61
61/61
66/66
40-42.5/41
38-41/38
35-37/35
40-42.5/41
38-41/38
35-37/35
2,000/2,000
2,000/2,000
1,400/1,400
158
137/196
78/88
59/69
First-class Compactness
in the Industry
First-Class Energy
Conservation in the Industry
Operation range of outdoor
temperatures
First-class Compactness
in the Industry
First-Class Energy
Conservation in the Industry
Daikin's HRV (Heat Reclaim Ventilation) recovers heat energy lost through ventilation and holds down room temperature changes
caused by ventilation, thereby maintaining a comfortable and clean environment. This also curbs the load on the air conditioning system
and conserves energy. In addition, the HRV is interlocked to Daikin's VRV system, SkyAir and other air conditioning systems and
automatically switches over ventilation mode, further increasing the effects of energy conservation. HRV operation has been centralized
on the air conditioner remote controller allowing total control over air conditioning and ventilation with a simple configuration.
Daikin's HRV (Heat Reclaim Ventilation) recovers heat energy lost through ventilation and holds down room temperature changes
caused by ventilation, thereby maintaining a comfortable and clean environment. This also curbs the load on the air conditioning system
and conserves energy. In addition, the HRV is interlocked to Daikin's VRV system, SkyAir and other air conditioning systems and
automatically switches over ventilation mode, further increasing the effects of energy conservation. HRV operation has been centralized
on the air conditioner remote controller allowing total control over air conditioning and ventilation with a simple configuration.
Indoor unit
Daikin air conditioner
LCD remote controller
for indoor unit
• Operating mode signal 
• Filter cleaning signal 
• Failure detection signal
• ON/OFF signal
• Cooling/Heating mode signal
• Set temperature signal
• Ventilation signal
• Humidifier ON/OFF signal
285 mm
Air Conditioning Load 
Reduced by Approximately 28%
1. Approximately 20% by operating
in total heat exchange mode (in
comparison with normal
ventilation fans)
2. Another approximately 6%
gained by auto-ventilation mode
changeover switching 
3. Yet another approximately 2% by
pre-cool, pre-heat control
The use of the originally developed High
Efficiency Paper (HEP) element and
optimized design of the fan and airflow
passages, has enabled the first-class
compactness in the industry while
maintaining some 28% reduction of air
conditioning load as before. The height
of the main unit has been reduced by up
to 285 mm* and easily fits in limited
spaces, such as behind ceilings.
HRV
Operation range of outdoor
temperatures
Cold climate compatible :
Standard operation at
temperatures down to -15°C
The new intermittent
operation mode is
activated when
outdoor temperature
goes down to -10°C
or below, preventing
freezing or
condensation in the
unit. Standard
models can now be
used in cold climate
regions.
-20
-10
0
10
20
30
40
50
50˚CDB
-15˚CDB
*
In case of VAM500FAVE.