Cautions PCV0320 1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced. 2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided and choose an outdoor unit with anti-corrosion treatment. http://splitoff.ru/tehn-doc.html , , , . Quieter, Smaller, Sleeker, Simpler: The is now four times better. Even earth friendly with a higher COP.
maller uieter impler leeker The is now four times better. Even earth friendly with a higher COP. Daikin has put comprehensive cutting-edge technologies into the VRV II, derived from its Customer First policy and 20 years of experience with the VRV system. The results are quieter operation, smaller units, sleeker design, and simpler installation and maintenance, with less impact on the environment with higher COP.
Wide range The new VRV II is a significantly improved version of the original VRV, which revolutionized building air conditioning. The latest in air conditioning technologies are applied to fulfill all the needs of our customers. The VRV II opens the door to the future of air conditioning. A maximum 48 HP with built-in flexibility This level of power is a quantum leap over the previous 30 HP, taking Daikin into the top rank of the industry.
Flexible design An incredible 50 %*1 reduction in installation space High external static pressure 6 mm H2O The VRV II has drastically reduced the installation space required, making it the most space saving system in the industry. Daikin now offers 6 mm H2O external static pressure specification as standard (previously 5 mm H2O as an option) to meet the requirements of veranda installation. *1.At 16 HP Easy installation RSXYP Transportation by Lift All units can be transported by lift.
High reliability Quiet operation Double backup operation in compressors and units Nighttime quiet operation function If one of the three compressors in an outdoor unit malfunctions, one of the other compressors takes over emergency operation. Furthermore, if one outdoor unit malfunctions in a system of more than 18 HP, other outdoor units provide emergency operation until repair is effected. 2 modes*1 with low operating sound level at night. Set on the outdoor PCB.
Offers a wide selection of models Conventional systems air condition a building as a whole, whereas the VRV system air conditions each room individually. Hence it is ideal for the constantly changing occupancy of a typical building. Even further, precise level control is possible that reacts to the exact conditions in each room. Individual control promotes a far more economical and efficient system. Lineup of heat pump types is 5 to 48 HP, and heat recovery types is 8 to 48 HP, both in 2 HP increments*.
The DAIKIN VRV system offers low running costs, considerable savings in both energy and space, and high reliability. The innovative inverter technology ensures sufficient air conditioning in every stage of operation. The VRV II series includes a Heat Recovery type, which allows simultaneous cooling and heating operation within the same refrigerant circuit, conserving even more energy by recovering the heat generated by the cooling operation and using it for heating.
Daikin's VRV systems include indoor and outdoor units available in a wide variety of models for all sizes of buildings and installation conditions. Long refrigerant piping lengths and other features put few restrictions on design for greater flexibility in meeting the needs of the building.
Unique piping and wiring systems and lightweight, compact indoor units make it possible for just a few people to install a VRV system quickly and easily. The Auto Address Setting function and the Auto Check function for piping and wiring errors allow anyone with just the ability to install Super Wiring System A Super Wiring system is used to enable the shared use of the wiring between indoor and outdoor units and the central control wiring.
The self-diagnosis function detects malfunctions in major locations in the system and displays the type of malfunction and location. This allows servicing and maintenance to be performed more efficiently. Operation lamp Inspection display Unit No.
Individual Control Systems Wired remote controller Wireless remote controller (Optional) (Optional) Large liquid crystal screen displays complete operating status. Digital display lets you set temperature in 1°C units. Lets you individually program by timer the respective times for operation start and stop within a maximum of 72 hours. Equipped with a thermostat sensor in the remote controller that makes possible more comfortable room temperature control.
Centralized Control Systems Up to 64 groups of indoor units (128 units) can be centrally controlled. System integration with various air-conditioning peripheral equipment such as HRV (Heat Reclaim Ventilation) is easy. Optional controllers for centralized control can be combined freely, and system can be designed in accordance with building scale and purpose. Central remote controller (Optional) 64 groups (zones) of indoor units can be controlled individually same as LCD Remote controller.
Advanced control systems The all-in-one color LCD controller offers high functionality in the smallest of size Up to 3 kWh meters Compact but powerful ! (with pulse output/locally procured ) Via internet *1 AIRNET SERVICE SYSTEM (Optional) PCMCIA Card Slot loading A/C power proportional distribution pulse input X 3 systems (Optional) For power proportional distribution VRV System DCS601B51 D -NET X 1 Line DCS601B51 Display or print out power distribution (User PC) Forced shutdown HRV Fire
Ceiling mounted cassette (double-flow) type Capacity range Type Model name 20 25 32 40 50 63 80 100 125 200 250 (0.8HP) (1HP) (1.25HP)(1.6HP) (2HP) (2.5HP)(3.
Ceiling mounted cassette (multi-flow) type 600 x 600 multi flow ceiling mounted cassette type FXFQ25M / FXFQ32M / FXFQ40M FXFQ50M / FXFQ63M / FXFQ80M FXFQ100M / FXFQ125M FXZQ20M/FXZQ25M/FXZQ32M FXZQ40M/FXZQ50M New Super Cassette type is compact, quiet and easy to install. Quiet, stylish unit with a horizontal blow capability Because of the light weight, suspension is easy.
Ceiling mounted built-in type Ceiling mounted cassette corner type FXSQ20M/FXSQ25M/FXSQ32M FXSQ40M/FXSQ50M/FXSQ63M FXSQ80M/FXSQ100M/FXSQ125M FXKQ25M / FXKQ32M FXKQ40M / FXKQ63M Slim design for flexible installation Single-flow type allows effective air discharge from corner or from drop-ceiling. Providing 3 different settings of standard, draft prevention and ceiling soiling prevention, the auto swing mechanism ensures even distribution of airflow and room temperature.
Ceiling mounted duct type Ceiling suspended type FXMQ40M/FXMQ50M/FXMQ63M FXMQ80M/FXMQ100M/FXMQ125M FXHQ32M/FXHQ63M/FXHQ100M High static pressure allows flexible duct design. Slim body with quieter and wider air flow More than 150Pa of external static pressure Adoption of newly designed SILENT STREAM FAN High external static pressure allows extensive duct work for flexible applications. Uses the new silent stream fan and many more silent technologies.
Wall mounted type Floor standing type FXAQ20M / FXAQ25M / FXAQ32M FXAQ40M / FXAQ50M / FXAQ63M FXLQ20M/FXLQ25M/FXLQ32M FXLQ40M/FXLQ50M/FXLQ63M Perfect unit for perimeter zone air conditioning. Sophisticated design and compact casing harmonized in any interior décor Compact and stylish design that does not detract from the decor of the room. Floor standing types can be hung on the wall for easier cleaning. Since running the piping from the back allows the unit to be hung on walls.
Heat pump type Between 8 (5 HP) and up to 40 (48 HP) indoor units in a single refrigerant piping circuit can be individually controlled in minimum increments of 2.2 kW (0.8 HP).
Ceiling Mounted Cassette Type Heat Pump Type HP Model name Combination Number of connectable indoor units 5 HP RXYQ5M RXYQ5M 8 8 HP RXYQ8M 13 10 HP RXYQ8M RXYQ10M RXYQ10M 16 12 HP RXYQ12M RXYQ12M 14 HP RXYQ14M RXYQ14M 16 HP RXYQ16M RXYQ16M 18 HP RXYQ18M 20 HP RXYQ20M 22 HP RXYQ22M RXYQ10M + RXYQ12M 24 HP RXYQ24M RXYQ10M + RXYQ14M 26 HP RXYQ26M RXYQ10M + RXYQ16M 28 HP RXYQ28M RXYQ30M RXYQ12M + RXYQ16M 30 HP 2,000 2,500 3,150 4,000 5,000 6,300 8,00
600X600 Multi Flow Ceiling Mounted Cassette Type MODEL 2,500 3,150 4,000 5,000 6,300 8,000 10,000 12,500 Btu/h (*1) 7,900 9,900 12,500 15,900 19,900 25,000 31,800 39,700 49,600 (*1) 2.3 2.9 3.7 4.7 5.8 7.3 9.3 11.6 14.5 (*2) 2.2 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.0 kcal/h 2,200 2,800 3,400 4,300 5,400 6,900 8,600 10,800 13,800 21,500 Btu/h 8,500 10,900 13,600 17,000 21,500 27,300 34,100 42,700 54,600 6.3 kW 2.5 3.2 4.0 5.0 6.3 8.0 10.0 12.
Ceiling Suspended Type Floor Standing Type/Concealed Floor Standing Type MODEL FXHQ32MVE FXHQ63MVE Power supply Cooling capacity FXHQ100MVE FXNQ20MVE FXNQ25MVE FXNQ32MVE FXNQ40MVE FXNQ50MVE FXNQ63MVE kcal/h(*1) 3,150 6,300 10,000 Btu/h(*1) 12,500 25,000 39,700 3.7 7.3 11.6 (*1) kW (*2) Cooling capacity FXLQ 3.6 7.1 11.2 3,400 6,900 10,800 Btu/h 13,600 27,300 42,700 kW 4.0 8.0 12.5 Air flow rate (Hi/Lo) m3/min 12/10 17.5/14 25/19.
Heat Pump Type MODEL Heat Pump Type RXYQ5MY1B RXYQ8MY1B RXYQ10MY1B kcal/h(*1) 12,500 20,000 25,000 Btu/h(*1) Power supply Cooling capacity RXYQ14MY1B RXYQ16MY1B 30,000 35,500 40,000 3 phase, 380 - 415V, 50Hz RXYQ34MY1B RXYQ36MY1B RXYQ38MY1B RXYQ40MY1B RXYQ42MY1B RXYQ44MY1B RXYQ46MY1B RXYQ48MY1B MODEL Constituent Model 49,500 78,900 98,700 118,000 141,000 157,000 (*1) 14.5 23.1 28.9 34.6 41.3 45.9 Power supply (*2) 14.0 22.4 28.0 33.5 40.0 44.
Heat Recovery Type MODEL Power supply Cooling capacity Heating capacity (*3) Capacity control Casing color Compressor Constituent Model kcal/h(*1) Btu/h(*1) (*1) kW (*2) kcal/h Btu/h kW % Motor output kW Air flow rate Dimensions(HXW XD) Sound level (380V) (*4) Refrigerant Refrigerant oil Refrigerant oil charge Piping connections m3/min mm dB(A) Liquid mm Suction gas mm Discharge gas mm Oil mm REYQ18MY1B REYQ20MY1B REYQ22MY1B REYQ24MY1B REYQ26MY1B REYQ28MY1B REYQ30MY1B REYQ32MY1B MODEL REYQ8MY1B RE
Ceiling mounted built-in type No.
Operation control system optional accessories FXFQ-M FXZQ-M FXKQ-M FXSQ-M FXMQ-M FXHQ-M FXAQ-M FXLQ-M FXNQ-M No.
Heat Reclaim Ventilation Models VAM150FAVE VAM250FAVE VAM350FAVE VAM500FAVE VAM650FAVE VAM800FAVE VAM1000FAVEVAM1500FAVE VAM2000FAVE Power Supply VE: 1 phase, 220-240V/220V, 50Hz/60Hz Temp. Exchange Efficiency (%) [50Hz/60Hz] Daikin's HRV (Heat Reclaim Ventilation) recovers heat energy lost through ventilation and holds down room temperature changes caused by ventilation, thereby maintaining a comfortable and clean environment.
R410A System/ Precautions on Installation Precautions R410A applies higher pressure than R22 and uses refrigeration oil different from R22. Therefore, piping works and tools are also different from those for R22 refrigerants. R22 Refrigerant Tools R410A (Single-component refrigerant) (Quasi-azeotropic mixture refrigerant) Refrigeration oil Condensing pressure Mineral oil (Suniso) Synthetic (ether) oil 1.84MPa (18.8kg/cm 2) 2.97MPa (30.