User`s manual

10
Diffu ser
3- Dimens ional blade
Qui e t de s i gn
Compact and aesthetic square panel type
Us es the newly devel oped "Diffus er Turbo Fan" with appli cati on
of aircraft technology.
Quiet operation is rea lized by a unified struct ure of 3-dimensional
blades and air diffus er for arranging the flow of air in the air
conditioner.
Uniformpanel size for all models.
The conventional 100– 140models ' rectangular panel types have all been
conve rted to the sa me comp act square type as the 50–71models. This
perm its smoo th interior harm ony of ceilings w ith the ligh ting fixtures.
Insta llatio n of mult iple air cond itioners o f different capacities will also be
FH(Y)C71K
35
dB
30
dB
FH (Y)C125K
42
dB
Indoor unit
Note: Operating s ound may increas e more than that when us ed with 3- way air flow
or 2- way air flow, or when us ed together with a optional kit.
High Low
36
dB
Top class of the industry
Super cassette type is more compact, lighter and
easier to install than the conventional types.
Maintainability also greatly improved.
Simplifies height adjustment of the main
unit.
Adjus tment pockets in the four corners of
the panel make height adjustment of the
main u nit much easier.
Main unit is lighter and more compact to
further sim plify i nstallation
Because of the light weight, suspens i on is possibl e without an
upper l i ft.
Provided with high lift drain
water lift-up mechanism
(Increasedlift of drain pipe up
to 750 mm from the ceiling).
The FH (Y)C50K– 71K are th in
models ( 230 mm) which can
be installed in narrow false
ceiling space.
Min . 245 mm
FH(Y)C100K– 140K
750 mm
Two Select thermo-sensors
Thermo-sens ors on both indoor unit and wired remote con-
troller (option). Temp erature d etection can b e set closer to
t he living a rea to further improve comfort le vel.
* Indoor unit' s thermo-s ensor must be used when the air conditioner is controlled
from another room. (Wireles s remote controller does not have a thermo-sens or. )
( FHYC125F)
100~140
50~71
50
()
9
There are 3 patterns in a uto swing operati on
Swings within the range of 10
°
to 65
°
.Swingangleissetfrom10
°
to 40
°
so
people are not s ubjected to strong winds
(Recommended where there are seats near
the air cond itioner).
Swing angle is w ithin a range of 30
°
to 65
°
to pre vent blowing against the ce iling . (Th is
recommended for those who are particular
about cle anliness of the ceiling).
10
°
10
°
40
°
40
°
30
°
30
°
65
°
65
°
10
°
10
°
65
°
65
°
Has been set to standard setting at time of shipment. This can be changed using the remote control.
Pattern
1
Standard s etting
CEILING-MOUNTED CASSETTE TYPE
Sound level
35/30
d
B
[High] [Low]
FHYC71K
CEILING MOUNTED CASSETTE TY PE
FH
(
Y
)
C50– 140K
Freedom of s elec tion of installation location
Since a multi-flow system is used, 4-wa y, 3-
way or 2-way air flow can easily be
selected, permitting in sta llatio n in
locations correspond ing to interior
Can also be installedin high ceilings.
Max. 4. 2 m
Pattern
2
Draft preventi on setti ng
Pattern
3
Setting to prevent soil ing of ceiling
Numb er of air flow outlets used
3-way
air flow
FH(Y)C50K–71K FH(Y)C100K–140K
3.0 m
3.3 m
3.5 m
3.5 m
3.8 m
4-way
air flow
2.7 m
Standard
High ceiling
High ceiling
3.0 m
3.5 m
3-way
air flow
3.6 m
4.0 m
4.2 m
2-way
air flow
2-way
air flow
4.2 m
4.2 m
4-way
air flow
3.2 m
3.6 m
4.2 m
Ceiling
height
Note: S et to s tandard 4-way air flow when shipped.
Hig h ceilin g types and will be set for
remote control operation.
Criteria for ceiling height and number of air flow outlets
Note : For 3-way or 2-way air flow installation,
the sealing member (option) for air
discharge outlet must be used to
close off the unused outlet(s).
(FHYC100K–140K)
Wired LCD remote controller Wireless LCD remote controller
Asignalreceivermustbe
added to the indoor unit.
Wireles s remote c ontroller and s igna l
rec eiver unit are s old as a s et.
Note: R emote controller c able not
inc luded. C a bles mus t be
proc ured loc ally.
Accessory required for indoor unit (option)
BRC1C61
Signal receiver unit
(Installed type)
BRC7C613W
(for c ooling only type)
BRC7C612W
(for heat pump type)