Specifications

Installation Manual ED72-975
46 BRC1E61
3P243521-1
18 English
Ɣ
If operation is not available due to any malfunction, refer to following
Failure diagnosis method
.
After the test operation fi nishes, check that Ɣ
error
code record is not displayed in the Service
Contact/Model Information screen of the main menu according to the following procedure.
CAUTION
7-14
Press Menu/Enter button in the basic
screen. Main menu screen is dis-
played.
Select
7-15
Service Contact/Model Info in
the main menu, and press Menu/Enter
button.
Service Contact/Model Information
7-16
screen is displayed. Check that error
code record is not displayed in the
screen.
Screen which does not display the
error code record means normal
status.
If the error code record is displayed,
7-17
conduct the failure diagnosis referring
to <Error code list> in the installation
manual of the indoor unit.
After the failure diagnosis fi nishes,
press and hold On/Off button for
4 seconds or longer in the “Service
Contact/Model Info” screen to erase
the error code record.
Failure diagnosis method
When the remote controller displays Ɣ
any item in following table, inspect the
details in the table.
If a error occurs, “code” is displayed in Ɣ
the LCD like right fi gure.
Conduct the failure analysis referring to
“Error code list” in the installation
manual of the indoor unit.
And when the unit No. which detected
the error during group control is
confi rmed, refer to “
8. Checking
procedure of error record
”.
<Basic screen>
147-
Set temperature
28°C
Cool
Return Setting
Press Menu/Enter button.
<Main menu screen>
157-
Return Setting
MainMenu
Set temp mode changeover
Airflow Direction
Quick Cool/Heat On/Off
Ventilation
Timer setting
Service Contact/Model Info
1/2
Press Menu/Enter button.
167-
177-
Return Setting
Error code:U5
Indoor unit
–––
/000
Outdoor unit
–––
/000
Contact address
0123
4567
8900
Press and hold On/Off
button for 4 seconds or
longer during backlight lit.
Set temperature
28
°C
Cool
Test Operat. CODE : U5
01_EN_3P243521-1.indd 18 2/3/2009 1:19:23 PM
English 17
7-6
Press On/Off button within about
10 seconds. The test operation starts.
Check operation condition for
3 minutes.
Note) In the case of above-men-
tioned procedures
7-5
and
7-6
in reverse order, test
operation can start as well.
Press Menu/Enter button in the basic
7-7
screen. Main menu is displayed.
In the case of a model having airfl ow
7-8
direction setting function, select
Airfl ow Direction in the main menu
and check that airfl ow direction is
actuated according to the setting.
For operation of airfl ow direction
setting, see the operation manual.
After the operation of airfl ow direction
7-9
is confi rmed, press Menu/Enter button.
Basic screen returns.
Press and hold Cancel button for
7-10
4 seconds or longer in the basic
screen.
Field setting menu is displayed.
Select
7-11
Test operation ON/OFF in the
eld setting menu, and press Menu/
Enter button. Basic screen returns and
normal operation is conducted.
Check the functions according to the
7-12
operation manual.
When the decorative panel is not
7-13
installed, shut off the power supply
after the test operation fi nishes.
If interior work is not completed after the Ɣ
test operation fi nish, explain to the
customer that operation should not be
performed until the interior work comple-
tion to protect the indoor unit.
(If the operation is performed, the
indoor unit may be contaminated with
the materials which arise from paints or
adhesives during the interior work, and
water splash or water leak may occur.)
67-
77-
Set temperature
28
°C
Cool
Test Operation
Press On/Off button
(within 10 seconds).
Press Menu/Enter button.
<Main menu screen>
87-
Return Setting
MainMenu
Set temp mode changeover
Airflow Direction
Quick Cool/Heat On/Off
Ventilation
Timer setting
Service Contact/Model Info
1/2
Press Menu/Enter button.
97-
Return Setting
Airflow Direction
Swing
Change the airfl ow
direction by using
(Up/Down)button.
Press Menu/Enter button.
107-
Set temperature
28
°C
Cool
Test Operation
Press and hold Cancel
button for 4 seconds or
longer during backlight lit.
117-
Return Setting
Field setting
Test operation ON/OFF
Register Service Contract
Field setting list
Group No. setting
Indoor unit Airnet No. set
Outdoor unit Airnet No. set
1/2
Press Menu/Enter button.
<Basic screen>
01_EN_3P243521-1.indd 17 2/3/2009 1:19:22 PM