Technical data

Sky Air • Intelligent Manager
77
5
5
5 Functions
5 - 2 Detailed Explanation of Functions
5 - 2 - 2 Control, Operation, Settings
(1) Login settings
Sets user operation authority to control the range of operation and view, consultation, read, read-only. When logging in, the users can operate the
intelligent Manager within their allocated authority.
30 users can be registered and passwords can be set individually.
When unmanned, this is set to a log-off status. Settings can also be set for the log-off status.
It is possible to limit personnel who may operate intelligent Manager to prevent mis-operation or unauthorized handling.
The following shows authorization levels that can be set.
(2) Individual Control
Allows manual, individual operation of starting and stopping of management items. Operations for starting and stopping, switching the operating mode,
changing the temperature settings, switching enable/disable of individual remote controllers and for resetting of the filter sign are possible when using
DIII-NET compatible air conditioners.
Items pressed later have priority with regard to management items defined by the schedule control and interlocking control.
(3) Collective starting/stopping and settings for control group
Registering a plurality of management items to a control group allows manual starting and stopping for all equipment. Operations for starting and
stopping, switching the operating mode, changing the temperature settings, switching enable/disable of individual remote controllers and for resetting
of the filter sign are possible when using DIII-NET air conditioners.
Items pressed later have priority with regard to management items defined by the schedule control and interlocking control.
Registers a maximum of 1024 management items in one group and a maximum of 200 groups.
Authorization When Authorized When Not Authorized
Running/Stopping/Setting Can perform run/stop/set operations Cannot perform run/stop/set
Schedule Registration Can inspection, register and edit schedules Can only inspect schedule
Interlock Control Registration Can inspection, register and edit link control Can only inspect link operation
Emergency Stop Registration
Can inspection, register and edit emergency stop Can only inspect emergency stop
Emergency Stop Canceling Can cancel emergency stop Cannot operate
Report Inspection Can inspect reports (daily, monthly annual) Cannot inspect
Report Registration Can set reports (daily, monthly annual) Cannot operate
History Operation Can inspect and set history Can only inspect history
System Settings Can set system Cannot operate
Subordinate Centralized Control Setting Can set centralized control Cannot operate
User Registration Can register users and set authority Cannot operate
Maintenance Mode Can set maintenance mode Cannot operate
Control, Operation, Settings
Login settings
Individual control
Collective starting/stopping and settings for control group
Schedule control
Interlocking control
Emergency stop control for fires
Power failure and recovery processing control
Centralized control of air conditioners