Technical data
• Sky Air • Intelligent Touch Controller
59
•
3
4
5
5 Specifications
6 Accessories
Intelligent Touch Controller DIII-NET Plus adapter
REFERENCE DCS601C51 DCS601A52
POWER SUPPLY externally supplied AC100V-240V, 50/60Hz externally supplied AC100V-240V, 50/60Hz
CONDITION OF INSTALLATION METHOD FOR USE JIS4 switchbox embedded in indoor wall -
OPERATING CONDITION Surrounding temperature 0
°
C to 40
°
C-10
°
C to 40
°
C
Humidity less than 85 % RH (if no condensation) less than 90 % RH
DIMENSIONS HxWxD mm 147x230x107 190x157x42
LCD PANEL Size / n
°
of dots / n
°
of colours 5.7 inches / QVGA 320x240 / 4,096 colours -
MAXIMUM NUMBER OF INDOOR GROUPS 1 x 64 (2 x 64: combined with DCS601A52) 1 x 64
MAXIMUM NUMBER OF OUTDOOR SYSTEMS 1 x 10 (2 x 10: combined with DCS601A52) 10
PC & DISPLAY built-in -
INPUT Touch panel 10 bit encoded analog input -
COMMUNICATION FUNCTIONS DIII-NET x 1 air conditioning equipment communication line air conditioning equipment communication line
Ethernet port for web access and e-mail function -
RS-232C DIII-NET Plus adapter -
10BASE-T web option -
Modem 999121A onboard modem capability -
PCMCIA slot flash memory card -
INPUT TERMINALS Digital input Di x 1 forced shutdown -
Pulse input Pi x 3 power measuring pulse power measuring pulse
OVERSEAS CERTIFICATION Safety of information - Technology Equipment IEC60730 (including IEC60335) IEC60730 (including IEC60335)
Interference (EMC) EN55022 Class A, EN55024 EN55022 Class A, EN55024
PROJECT DATA & ENGINEERING Configuration and engineering for each project are necessary. For further details, please consult with Daikin
distributors and dealers
Description Reference Comments
SOFTWARE DCS002C51 Power Proportional Distribution (PPD) Software
DCS004A51 E-mail / Web software
DCS007A51 Http interface option
HARDWARE DCS601A52 DIII NET-Plus adapter
TOUCH-PEN 1264009 Spare part n
°
of Touch-Pen for Intelligent Touch Controller
INTERFACE ADAPTERS KRP928A2S For connection to Split units
DTA102A52 For connection to R-22 / R-407C Sky Air units
DTA112B51 For connection to R-410A Sky Air units
DIII-AI DAM101A51 Outdoor temperature sensor, required for free cooling changeover
DIGITAL INPUT DEC101A51 Input contacts: 8 inputs wth additional error feedback
DIGITAL INPUT/OUTPUT DEC102A51 Output contacts: 4 points with additional error and on/off feedback