Sky Air Network Solution
48
3
1
1 Features & Outline
Basic solution for control and management of Sky Air and VRV systems
Application area
Critical applications for centralized monitoring.
System functions
Automates alarm (report messages) for any malfunctions/ errors. Immediate report of any indoor unit breakdown to the servicing company.
Minimizes the inconvenience of not having air conditioning via rapid messages.
Functions via mobile phone
Status monitoring and control (Start/Stop, Set temperature, Operation mode, Room temperature, Operation time, Error code)
Error notification
Functions when standing alone
Rotation function
Back-up operation
2 Main Functions
A single DS-NET Adapter unit can monitor and control the air conditioners of up to 4 remote control groups.
The following functions of air conditioners can be monitored and controlled by mobile phone:
O: Possible
X: Impossible
3 Specifications
Daikin recommends the use of a Wavecom Fastrack modem
Item
Monitoring Operation
Start/Stop
oo
Operating mode (Fan/Cool/Heat)
oo
Temperature setting (Cool/Heat)
oo
Error code
ox
DTA113B51
Supply - Voltage DC 16V supplied from R/C line
Maximum number of connectable indoor units 4 units per adapter PCB (via GSM)
Forced ON/OFF input Non-voltage (normal) ‘a’ contact x each point
Dimensions (mm) 100x100x35
Installation method Built into the indoor unit or placed inside a box especially built for it
Communication functions via GSM RS232C, GSM modem
Ambient temperature/humidity conditions for operation -10 ~ 50°C, max. of 95% RH
Control functions via GSM Start/stop, operation mode (fan/cool/heat), temperature setting
Monitoring functions via GSM Start/stop, operation mode (fan/cool/heat), temperature setting, error code
Malfunction monitoring functions Malfunction reporting function
Automatic alternating operation functions via GSM Yes
Back-up operation functions via GSM Yes