6
6 Wiring example of centralised control systems
• Be sure to connect the wiring of the central controller to (A) or (B).
(Connect to (B), if it is possible.)
• Be sure to limit the number of indoor units within the limitation for each system.
• Never connect the wire between the controllers, that are connected to different circuits.
• In order to prevent the connection of 3 wires on the same terminal, connect to the terminal unit of (A) or (B), or use the relay terminal
(local supply).
Pattern 1
Pattern 2
?• When all centralised control systems are located at several places.
?• When all centralised control systems are located at one place.
or
Unified On/Off Control
(DCS301B51)
Up to 4 control
can be connected.
Centralised remote
control
(DCS302B51)
Forced
shut-down
input
Unified adapter for computerised
control (DCS302A52)
(6)
(Max 7)
Schedule timer (DST301B51)
Possible to set 8 different patterns of weekly schedule by one unit.
Possible to interlink with building management
system (Host computer monitor panel.)
Unified On/Off control
(DCS301B51)
Up to 4 controllers can be
connected.
Centralised remote control
(DCS302B51)
Never connect the wire
between the
controllers, which are
connected to
different circuits.
or
or
or
The schedule timer,
unified adapter for
computerised control
etc. can be connected to
the same as in pattern 1.