Technical data

Sky Air Centralised Control systems
39
Centralised control systems
2
5
5 Survey of various control systems
For more effective localized environmental control Daikin offers various control systems such as single or double remote control or centralized control.
This enables the construction of a variety of operational control systems which can be adapted for various uses from remote control to building
automation (BA).
Control Method Objective / use System outline Function Standard number of units
DST301B51
Schedule timer
To carry out weekly
schedule operation by 1-
minute units
ON/OFF time can be set by units of day, hour and
minute; ON/OFF pattern can be set by time zone of
twice per day in accordance with application.
Simultaneously controls 64
groups with one schedule timer.
Max. 128 units
Centralised remote
control DCS302B51
To control all indoor units
from one place
Double central control function
Function of liquid crystal remote control can be
controlled individually for each zone of the indoor
unit.
Individual/ unified operation
Up to 8 patterns can be set for operation controlled
by programmed time when used in combination
with schedule timer.
Temperature setting for each zone
Control operation for each room during centralized
control
Remote control operation rejected command
Sequential start function
Controls up to 64 groups with one
centralised remote control.
Max. 128 units
Unified ON/OFF control
DCS301B51
Double central control function
Indoor unit ON/OFF control
Individual/unified operation
Remote control operation rejected command.
(Centralised remote control given priority when
used in combination with centralised remote
control.)
Sequential start function
Controls up to 16 groups of indoor
units with one unified ON/OFF
control.
Max. 128 units
Schedule timer
Centralised
remote control
Unified ON/OFF
control
Respective functions of schedule timer,
centralised remote control and unified ON/OFF
control are possible.
(Control mode of centralised remote control is
given priority for operation of remote control for
indoor unit.)
Sequential start function.
Controls up to 64 groups of indoor
units with 1 schedule, timer,
2 centralised remote controls and
8 unified ON/OFF controls.
Max. length of transmission wiring for centralised control: 1 km
Schedule timer
(Power supply for
schedule timer)
Up to 128 indoor
units can be controlled
Max. length of transmission wiring for centralised control: 1km
Single phase,
220~240V
power supply
Centralised remote
control
Up to 64 units by
individual control
Remote control Remote control
Up to 64 groups (128 units) can be
controlled by group control.
Max. length of transmission wiring for centralised control: 1 km
Single phase
220~240 V
power supply
Unified ON/OFF
control
Up to 16 units by
individual control
Remote control Remote control
Up to 16 groups (128 units) can
be controlled by group control.
Schedule
timer
Centralised remote
control
Combination of up to 8 unified
ON/OFF controls possible
Up to 128 units by
individual control
Remote control
Remote control
Up to 64 groups (128 units)
can be controlled by
group control.
Single phase, 220~240V power supply