Technical data

Sky Air • BACnet Interface
127
3
7
9
9 Function
9 - 4 Major functions of air-conditioner devices
NOTES
1 *1: Remote control mode is for acceptance or rejection of on/off operation, temperature setting and air conditioning mode setting by remote control.
2 *2: If set locally, the host is not notified. Thus, monitoring cannot be accomplished from the host.
3 The meaning of 0, Χ are as follows
0: Possible functions
Χ: Impossible functions
Function
Air-conditioning equipment
Remarks
VRV Inverter
series
Interface adapter
for Sky Air series
(SA Heat Pump)
HRV
Wiring adapter
for other
air-conditioners
Start/stop control and monitoring
0000
Air-conditioner error notification
0000
Indoor air temperature monitoring
00ΧΧ
Temperature setting and monitoring
00
16~32
ΧΧ
Air-conditioning mode setting and monitoring
00ΧΧ
Air-conditioning mode switching is effective only for indoor
units for which cool/heat selection is permitted.
*1 Remote control mode setting and monitoring
00ΧΧ
Filter sign monitoring and reset
0 ΧΧΧ
Cumulative power value monitoring
Χ0
Thermostat status monitoring
0 ΧΧΧ
Compressor operation status monitoring
0 ΧΧΧ
Indoor fan operation status monitoring
0 ΧΧΧ
Heater operation status monitoring
0 ΧΧΧ
Air direction setting and monitoring
0 ΧΧΧ
Air flow rate setting and monitoring
0 ΧΧΧ
Forced thermostat off setting and monitoring
0
*2
ΧΧΧ
Forced thermostat on setting and monitoring
0
*2
0
*2
ΧΧ
Energy efficiency command (Setting temperature
shift)
0 ΧΧΧ