Technical data

Sky Air • LonWorks Interface
114
6
5
5 Survey of Functions
Function Description
Controlling items
ON/OFF Command Starts/stops air conditioner operation.
Operation Mode Setting Sets operation mode (heating/cooling/ventilation/auto).
Temperature Setting Sets room temperature.
Airflow Rate Setting Sets airflow rate.
Filter Sign Reset Resets filter sign.
Forced Thermostat OFF Setting Sets forced thermostat OFF.
Remote ON/OFF Control Rejection Sets whether permit/prohibit ON/OFF control rejection of the air conditioner with a hand-held remote
control.
Remote Operation Mode Control Rejection Sets whether permit/prohibit operation mode control rejection of the air conditioner with a hand-held
remote control.
Remote Temperature Setting Control Rejection Sets whether permit/prohibit room temperature setting control rejection of the air conditioner with a
hand-held remote control.
System Forced OFF Setting Forcibly stops the air conditioner connected to the DIII-NET /Resets the Forced OFF setting.
Sub Group Address Control Rejection Setting Permits/prohibits controlling of the centralized device connected to the DIII-NET.
Monitoring items
ON/OFF Status Report Monitors ON/OFF status of the air conditioner.
Operation Mode Status Report Monitors operation mode status (heating/cooling/ventilation) of the air conditioner.
Temperature Setting Report Monitors the set room temperature.
Room Temperature Report Monitors the room temperature.
Airflow Rate Setting Report Monitors the set airflow rate.
Filter Sign Report Checks limit of filter use and monitors if it has reached the limit.
Error Status Report Monitors error status of the air conditioners.
Error Code Report Displays the manufacturer-specified error codes if any errors occur.
Thermostat Status Report Monitors whether the air conditioner’s thermostat is working.
Forced Thermostat OFF Setting Status Report Monitors the forced thermostat OFF status.
Remote ON/OFF Operation Rejection Report Monitors the status if the air conditioner is permitting/prohibiting remote ON/OFF control with a hand-
held control.
Remote Control Operation Mode Setting Rejection Report Monitors the status if the air conditioner is permitting/prohibiting remote control operation mode with a
hand-held control.
Remote Control Temperature Setting Operation Rejection Report Monitors the status if the air conditioner is permitting/prohibiting remote control temperature setting with
a hand-held control.
System Forced OFF Setting Report Monitors the status of the forced OFF setting of the air conditioner connected to the DIII-NET.
Sub Group Address Control Operation Rejection Setting Report Monitors the status if the air conditioner is permitting/prohibiting control of a centralized device
connected to the DIII-NET.
A/C Communication Status Report Monitors the communication status (No Occupancy/ Communication normal/ Communication error) of
the air conditioner.