Technical data
• Sky Air • LonWorks Interface
113
•
6
4
4 Unlimited site size
The new network adapter can be connected to up to 64 groups, depending on the number of control and monitoring functions used :
300 > (number of indoor units) x (number of SNVT)
Maximum value is set by the LON BMS manufacturer: in this case 300
Number of connected indoor units: 1 ~ 64.
SNVT: Number of LON network variables