10 Explanations of Power Proportional Distribution
10 - 2 Count Accuracy
10 - 2 - 1 Cause of error
System example
<Case of arising error>
1 + Count conclusive total for indoor unit #1~#8 Refer to the next page
2 Count conclusive total for indoor unit #1~#5
Count conclusive total for indoor unit #6~#8 Refer to the next page
1 Count conclusive total for indoor unit #1~#8*: The reason to get and the error size.
REASON 1
iPU counts every one hour’s power consumption.
Though fraction in case of computation occurs at this time, it is computed after leaving off a 1-W figure to avoid the risk for the owners. As a result, the
error by the leaving-off occurs by 0.5W/ hour in average value of all indoor units.
Calculation example
(1) Count for errors in 8-day
Tenant A + B : 0.5 (Wh) × 24 hours × 8 days × 5 units = + 0.480 kWh
Tenant C : 0.5 (Wh) × 24 hours × 8 days × 3 units = + 0.288 kWh
total = + 0.768 kWh
(2) Assuming that the reads on watthour meters are as follows:
W1: read on watthour meter = 490 kWh
W2: read on watthour meter = 200 kWh
total = 690 kWh
(3) Finally it is concluded as total error = 0.768/690 × 100 = 0.11%