Technical data

64
• Control systems
• intelligent Touch Manager • ED721208
<DIII MASTER>
To set the iTM plus adaptor to SLAVE, use the DIII MASTER
switch.
Placing the switch in the upper position (labeled as “SLAVE”)
changes it to a SLAVE.
SLAVE
MASTER
To install multiple centralized controllers, set only the highest priority controller to MASTER and all other controllers to SLAVE according
to the following order of priority:
High
(1) Interface for use in BACnet
(2) Interface for use in LONWORKS
(3) intelligent Touch Manager (Main), iTM plus adaptor (Main)
(4) Central Remote Controller (Main)
(5) intelligent Touch Manager (Sub), iTM plus adaptor (Sub)
(6) Central Remote Controller (Sub)
(7) ON/OFF Controller (Main)
(8) ON/OFF Controller (Sub)
Priority
Low
Centralized
controllers that
cannot be installed in
parallel with iTM plus
adaptor
•CALCULATEUNIT
•intelligentProcessingUnit
•ParallelInterface
•IntelligentTouchController
•DIII-NETPlusAdapter
•ResidentialCentralRemoteController
•ScheduleTimer
•WiringAdaptorforElectricalAppendices(1)(KRP2)
Connecting contact or pulse input equipment such as electric energy meters
The iTM plus adaptor can be connected with an external signal input device for stopping air conditioners in an emergency, or with electric
energy meters for calculating the electricity usage of individual air conditioners (when power distribution is enabled).
WARNING
Be sure to perform this procedure with the power supply turned off. Not doing so may cause
an electric shock.
Do not clamp the cables with high-current lines such as a power cable.
NOTE
Power distribution is available for a maximum of 64 air conditioners (indoor units) per DIII-
NET port.