Technical data
59
• Control systems
• intelligent Touch Manager • ED721208
The table below shows the status of the CPU ALIVE/ALARM LED when the iTM plus adaptor is operating normally or failed.
NOTE
[LED status and operation table]
Operating condition CPU ALIVE ALARM
Normal Blink Off
Hardware failure Off On
Address failure On On
plus ADP IF communication failure On Blink
Determining installation place
Be sure to install the iTM plus adaptor in a place that meets the conditions described in 1.4.1 through 1.4.3.
Installation place and mounting direction
Note that the iTM plus adaptor must be installed in a place and in a mounting direction as described below:
•Installationplace:Indoor,insidecontrolenclosure(whichmustbelockableordesignedtobeopenedonlywithaspecialtool)
•Mountingdirection:Verticalonly
Required space
To install the iTM plus adaptor, the following space is required. Also note the following:
•Makesurethatthereisaminimumclearanceof20mmbetweeneachunitandwiringducts.
•Wheninstallingtwoormoreunitssidebyside,theycanbearrangedwithoutclearanceinthehorizontaldirection.
Required installation
space
40mm
40mm
20mm
20mm
20mm
A
A
160mm
149.2mm
A Wiring duct
Environmental conditions
The installation environment must meet the following conditions:
•Ambienttemperature:–10to50°C
•Ambienthumidity:85%RHorless(withoutcondensation)