Technical data

55
• Control systems
• intelligent Touch Manager • ED721208
Terminals location and conceptual connection diagram
Connect the contact input lines or pulse signal lines to the Di1, Di2, Di3, Di4, and COM terminals of the orange connector located on the
rear face. Each terminal has a different function.
[Di1] Emergency stop input
[Di2] [Di3] [Di4] Pulse input, contact signal input
[COM] Common
This function assignment, however, may be changed at a later time. For how to change the function assignment, refer to the commissioning
manual.
<Conceptual drawing of Di
connection>
NOTE
The COM terminals are all connected internally. So, you
can use either of them.
However, you can connect up to two wires simultaneously
to each COM terminal.
Di1
COM
Di2
COM
Di3
COM
Di4
COM
Requirements that must be met
•Cabletype:CPEVcable
•Corethickness:φ0.65-0.9mm
•Cablelength:200metersorless
<Pulse width>
•Pulsewidth:20to400ms
Pulse interval: 100 ms or more
A
B
A Pulse width: 20 to 400 ms
B Pulse interval: 100 ms or more
CAUTION
The contact connected to the contact input terminal must be capable of handling 10 mA at
16 VDC.
If an instantaneous contact is used for triggering an emergency stop, use one that has an
energization time of 200 ms or more.
Do not clamp the cables with high-current lines such as a power cable.
NOTE
When emergency stop input signal is enabled, you cannot restart all the air conditioners unless you
disable it.