Technical data

53
• Control systems
• intelligent Touch Manager • ED721208
Connecting I/O module
The intelligent Touch Manager can be used in conjunction with the I/O module. The I/O module provides a maximum of 960 I/O points
for controlling non-DAIKIN peripheral equipment such as lighting equipment and security lock systems.
WARNING
•Besuretoperformthisprocedurewiththepowersupplyturnedoff.Notdoingsomaycausean
electric shock.
•Donotclampthecableswithhigh-currentlinessuchasapowercable.
Terminals location and conceptual connection diagram
<Conceptual drawing of I/O module connection>
MONITOR
RS-485
A
A Max. 30 nodes
ConnecttheI/OmoduletotheRS-485terminalslocatedontherearface.Besuretoconnectthepositive(+)coretothe+(positive)
terminal and the negative (–) core to the – (negative) terminal, respectively. If you are using shielded stranded wire cables, twist and
connect the strands of wire to the G (Ground) terminal.
Requirements that must be met
•Cabletype:CPEVorFCPEVcable(shieldedtypealsoacceptable)
•Cablelength:500metersorless
•Corethickness:φ0.65-0.9mm
•Limitationincontactspernodeis120orless.Maximumnumberofnodesis30.
•TheintelligentTouchManagermustbeconnectedasaterminaltotheRS-485wiring.