Technical data
34
• Control systems
• Centralised control systems • DCS601C51 •
3D047623
Accessories
DEC102A51 - Digital input / output
Dimensional drawing
Mounting hole (*1)
(198)
(309)
325
335
70 70
70
70
1
6
4.5
40 40
140
40
80 40
325
UP
Spare hole (*1)
Mounting hole (*1)
Service entrance - wire lead-in port
(Approx. 10mm dia. x 6)
Fix the DEC102A51 firmly with
the installation screws (M4)
Spare hole (*1)
Front panel screw
DEC102A51
DEC102A51 DEC102A51
DEC102A51 DEC102A51
Power supply specifications 1~200-240V 50/60Hz
Rated power consumption 15W
Mass (Weight) 2.5kg
Case material Plated steel sheet
Case color Matting chrome
Notes
1 Installation place
•Installtheunitindoorswhereitisnot
exposed to water and dust or dirt.
•Installtheunitwhereboth
temperature and humidity do not
become high.
(Operating (available) temperature:
-10~+40°C
Operating (available)
humidity: 10~85%)
•Connectthewiringtobeconnectedin
the field from the lower surface side.
It is, therefore, necessary to make
arrangements so as not to attach
other equipment within 80mm from
the lower surface of this equipment.
•Installthisequipmentina
place in which only authorized
personnel can touch it.
2 Installation Direction
Install this equipment vertically to the
floor surface. It should be noted that
if it is installed in horizontal direction,
a malfunction or failure may result.
3 Installation Method
Ensure that this equipment is installed
with 4 screws (screw size M4 min.).
4 Restrictions in continuous installation
In case several devices are set up and
installation inside the power board is
carried out, each equipment installation
space and space between the wall
surface and this equipment should
be left at least as shown to the left.