Technical data

25
• Control systems
• Centralised control systems • wiring details
Length of transmission wiring
Flow chart to determine the number of units to be connected
Notes
1 Condition
(A) means:
•Centralcontrolequipment+Indoorunits+Outdoorunits+otheradapters£160units
•Conversionnumberofcentralcontrolequipment+Indoorunits+Outdoorunits+otheradaptors£200units
(B) means:
In case of connecting to DIII-NET
•Outdoorunitsmustbecountedtoonesystemevenincaseofincluding3units.(Master+Master+Master=Onesystem)
•TheoutdoorunitsconnectedbyterminalEx.Q1,Q2(exceptingterminalF1,F2)areregardedasonesystem.
2 When one system is to be controlled from two locations, up to two intelligent Touch Controller (In case of combining the intelligent
Touch Controller and Central Remote Controller, it is restricted to combine two Controllers in total), four Central Remote Controller
and 16 unified ON/OFF Controller can be connected. However, the maximum number of units that can be controlled is 128.
3 When a BS unit is used, the indoor units used in its downstream are not counted.
4 One port of one Interface for use in BACnet can have up to 64 groups (64 master indoor units with address). In case of adopting group
controlling, the circuit covered by the data station can have up to 128 indoor units including main and sub units.
Check sheet for number of units in one system
Centralised controller
Unit
Outdoor unit
No. of IPU of intelligent Manager
Intelligent Touch Controller (Note 2)
Central remote control (Note 2)
Unied ON/OFF control
Schedule timer
Interface for use in BACnet
®
(Note 3)
Interface for use of LONWORKS
®
Parallel interface
Qty Y/N
Qty Y/N
Qty Y/N
Qty Y/N
1
x 10
x 10
x 1 (A)
x 10
x 10
x 10
2
2
8
1
1
1
4
7
128
10(B)
10
200
8
Total
Total
Total
Total
=
=
=
=
=
=
=
+++
VRV
Single units and Multi systems
HRV (VAM)
Wiring adapter for other air conditioner
BS unit (Note 4)
Optional DIII Ai unit
SkyAir with adapter for certain units, please contact your dealer for this.
Other adapters
External control adapter for outdoor unit
Wiring adapter for electrical appendices (1)
Di unit
Dio unit
8 x
4 x
Ai unit