Technical data
124
• Control systems
• Standard protocol interfaces • BACnet Interface
Function
Major functions of air-conditioner devices
Function
Air-conditioning equipment
Remarks
VRV Inverter
series
Interface adapter
for Sky Air series
(SA Heat Pump)
HRV
Wiring adapter
for other
air-conditioners
Start/stop control and monitoring 0 0 0 0
Air-conditioner error notification 0 0 0 0
Indoor air temperature monitoring 0 0 X X
Temperature setting and monitoring 0 0 16~32 X X
Air-conditioning mode setting and monitoring 0 0 X X
Air-conditioning mode switching is effective only for
indoor units for which cool/heat selection is permitted.
*1 Remote control mode setting and monitoring 0 0 X X
Filter sign monitoring and reset 0 X X X
Cumulative power value monitoring 0 X X 0
Thermostat status monitoring 0 X X X
Compressor operation status monitoring 0 X X X
Indoor fan operation status monitoring 0 X X X
Heater operation status monitoring 0 X X X
Air direction setting and monitoring 0 X X X
Air flow rate setting and monitoring 0 X X X
Forced thermostat off setting and monitoring 0 *2 X X X
Forced thermostat on setting and monitoring 0 *2 0 *2 X X
Energy efficiency command (Setting temperature shift) 0 X X X
Notes
1 *1: Remote control mode is for acceptance or rejection of on/off operation, temperature setting and air conditioning mode setting by
remote control.
2 *2: If set locally, the host is not notified. Thus, monitoring cannot be accomplished from the host.
3 The meaning of 0, C are as follows
0: Possible functions