Technical data

111
• Control systems
• intelligent Touch Manager • ED721208
Wiring Length
• Totallengthmustbe2000morless.(Thetotalwiringlengthis1500mwhenshieldedwireuse.)
• Max.lengthmustbe1000morless.
[Example]
200m
100m
Indoor unit
500m
10m
10m
200m
Outdoor unit
Max. length
200+10+10+500
=720m
Total length 2000m
Max. length 1000m
Therefore, the limitations
on length are satisfied.
Total length
200+100+500+10+10+200
=1020m
Centralized
Control
Equipment
Recommendation of Installation DIII-NET Expander Adaptor
Intelligent buildings in recent years have increased in the amount of communication equipment and power supply wiring and this may
have an effect on DIII-NET communications. In the cases listed below, it is recommended that the “DIII-NET Expander Adaptor (DTA109A51)
be installed.
• Wherethereare8ormoreoutdoorunitsystems
• WhereitisnotpossibletoverifythatrestrictionsonDIII-NETwiringlength,branchedwiringandwiretypesareobserved
Wiring Specifications of DIII-NET
Be sure to use either 2-core sheathed vinyl cord or cable as mentioned below.
• Vinylcabtireroundcord VCTF JISC3306 <Example>Sectionofcord
• Vinylinsulated,vinylsheathedcableforcontrol CVV JISC3401
• Roundvinylsheathedcableforcontrol CVS JISC3401
• Roundvinylinsulated,vinylsheathedcable VVR JISC3342
• 600Vvinylcabtirecable VCT JISC3312
• Polyethyleneinsulatedvinylsheathedcable CPEV()
• Meshinsulatedcable MVVS()
When the shield wire is used, be sure to ground the one side of the shield wire.
Do not use the shield wire with other type of wire in the same system.
• Thetotalwiringlengthis1500mwhenshieldedwireisused.