Technical data

101
• Control systems
• intelligent Touch Manager • ED721208
Count Accuracy
(1) Cause of error
(System example)
Watthour meter
(with output)
Power supply
3 phase
#1 #2 #3 #4 #5 #6
#: Indoor unit's address
#7 #8
W2
W1
Outdoor unit
Tenant A Tenant B Tenant C
Legend
: Read on wattmeter
iTM
<Case of arising error>
W1+W2
Count conclusive total for indoor unit #1~#8 Refer to the “REASON”
W1 ≠ Count conclusive total for indoor unit #1~#5
W2 ≠ Count conclusive total for indoor unit #6~#8
Refer to the next page
W1+W2
Count conclusive total for indoor unit #1~#8* : The reason to get and the error size
REASON
iTM counts every one hours power consumption.
Though fraction in case of computation occurs at this time, it is computed after leaving off a 1-W figure to avoid the risk for the owners.
As a result, the error by the leaving-off occurs by 0.5W/ hour in average value as per each indoor unit.
(Calculation example)
(1) Count for errors in 8-day
TenantA+B:0.5(Wh)×24hr×8days×5units=+0.48kWh
TenantC:0.5(Wh)×24hr×8days×3units=+0.288kWh
total=+0.768kWh
(2) Assuming that the reads on watthour meters are as follows:
W1:readonwatthour meter =490kWh
W2:readonwatthour meter =200kWh
total =690kWh
(3) Finallyitisconcludedastotalerror=0.768/690×100=0.11%
W1 ≠ Count conclusive total for indoor unit #1~#5 :
W2 ≠ Count conclusive total for indoor unit #6~#8 :