Specifications
ED04-805 Capacity Tables
Room Air Conditioners E-Series 19
8. Capacity Tables
8.1 Cooling Only
FTKS25EVMA + RKS25EBVMA (50Hz 220-230-240V / 60Hz 220-230V)
3D054239A
FTKS35EVMA + RKS35EBVMA (50Hz 220-230-240V / 60Hz 220-230V)
3D054240A
AFR 8.7
BF 0.24
INDOOR
OUTDOOR TEMPERATURE(°CDB)
20 25 30 32 35 40
EWB EDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
°C °C kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
14.0 20 2.56 1.93 0.46 2.44 1.87 0.50 2.33 1.82 0.55 2.28 1.79 0.57 2.21 1.76 0.59 2.10 1.70 0.64
16.0 22 2.68 1.90 0.46 2.56 1.84 0.51 2.44 1.79 0.55 2.40 1.77 0.57 2.33 1.74 0.60 2.21 1.69 0.64
18.0 25 2.79 1.99 0.47 2.68 1.94 0.51 2.56 1.89 0.55 2.51 1.87 0.57 2.44 1.84 0.60 2.33 1.80 0.64
19.0 27 2.85 2.11 0.47 2.73 2.06 0.51 2.62 2.01 0.56 2.57 1.99 0.57
2.50 1.96 0.60 2.38 1.92 0.64
22.0 30 3.02 2.03 0.47 2.91 1.99 0.52 2.79 1.95 0.56 2.74 1.93 0.58 2.67 1.91 0.60 2.56 1.86 0.65
24.0 32 3.14 1.98 0.47 3.02 1.94 0.52 2.90 1.90 0.56 2.86 1.89 0.58 2.79 1.86 0.61 2.67 1.83 0.65
Symbols NOTE:
AFR : Air flow rate (m³/min.) 1. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 7.5m
Level difference : 0m
2. shows nominal (rated) capacities and power input.
BF : Bypass factor
EWB : Entering wet bulb temp. (°C)
EDB : Entering dry bulb temp. (°C)
TC : Total capacity (kW)
SHC : Sensible heat capacity (kW)
PI : Power input (kW)
AFR 8.9
BF 0.24
INDOOR
OUTDOOR TEMPERATURE(°CDB)
20 25 30 32 35 40
EWB EDB TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI
°C °C kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW kW
14.0 20 3.31 2.33 0.78 3.31 2.33 0.86 3.26 2.31 0.93 3.19 2.27 0.96 3.10 2.22 1.01 2.93 2.13 1.08
16.0 22 3.75 2.44 0.79 3.58 2.35 0.86 3.42 2.27 0.94 3.36 2.24 0.97 3.26 2.19 1.01 3.10 2.11 1.09
18.0 25 3.91 2.52 0.79 3.75 2.44 0.87 3.58 2.37 0.94 3.52 2.34 0.97 3.42 2.29 1.02 3.26 2.22 1.09
19.0 27 3.99 2.63 0.79 3.83 2.55 0.87 3.66 2.48 0.94 3.60 2.45 0.97
3.50 2.41 1.02 3.34 2.33 1.10
22.0 30 4.23 2.53 0.80 4.07 2.46 0.88 3.90 2.39 0.95 3.84 2.37 0.98 3.74 2.33 1.03 3.58 2.26 1.10
24.0 32 4.39 2.45 0.81 4.23 2.39 0.88 4.07 2.33 0.96 4.00 2.30 0.99 3.90 2.27 1.03 3.74 2.21 1.11
Symbols NOTE:
AFR : Air flow rate (m³/min.) 1. Capacities are based on the following conditions.
Corresponding refrigerant piping length : 7.5m
Level difference : 0m
2. shows nominal (rated) capacities and power input.
BF : Bypass factor
EWB : Entering wet bulb temp. (°C)
EDB : Entering dry bulb temp. (°C)
TC : Total capacity (kW)
SHC : Sensible heat capacity (kW)
PI : Power input (kW)