Specifications

■Setting procedure: AKZ
Operation mode and setting method
0*1
1*1
2*1
3*1
4*1
5*1
6−
7−
8*3
9*2
*1. If the thermistor is not connected or has a broken wire, 99.9 is displayed.
*2.
With the default setting, 0 is displayed. Note that display is enabled when parameter n020 is “1” or the optional communication expansion board is installed.
*3. This is the value obtained by rough calculation under the following conditions (the error is around 20%): power supply voltage of  
200 V, pump discharge pressure of 0.2 MPa (VG32: oil temperature 25℃). Contact us separately about pumpless units.
Machine body temperature 【Th1】
Outlet oil temperature or return oil temperature 【Th2】
Room temperature 【Th3】
Inlet oil temperature 【Th4】
Reserved 【Th5】
△T(Th4∼Th2)
Cooling capacity control command value (%)
Compressor inverter rotational speed (rps)
Power consumption (kW)
Extended DIN (hundreds digit), DOUT (tens digit) status
Press the
[ENT] key
to switch
between
“Mode
and
“Data .
9
AKZ
SERIES
22
Supporting
information
Outlet oil temperature or return oil
temperature control, room
temperature synchronous control
Supporting information
Operation mode and setting method
AKZ 9 Series
Note) 1. Modes 2, 7, and 8 cannot be used on this series. Note) 2. Refer to Page 19 for details of necessary optional parts.
Mode No.
Mode name Description
Necessary optional part
Setting temperature range
Inlet oil temperature, room
temperature synchronous control
Keep the inlet oil temperature at the setting temperature
within the range specified in the right column.
Between Room temperature
-9.9℃ and Room temperature + 9.9℃
Inlet oil temperature, machine
temperature synchronous control
Machine temperature
synchronous thermistor
Between Machine temperature
-9.9℃ and Machine temperature+ 9.9℃
Between Machine temperature
-9.9℃ and Machine temperature + 9.9℃
Between Room temperature
-9.9℃ and Room temperature + 9.9℃
Mode 0
Inlet oil temperature,
fixed temperature control
Keep the inlet oil temperature at the setting temperature
within the range specified in the right column.
Mode 3
Keep the inlet oil temperature at the setting temperature
within the range specified in the right column.
Mode 4
Keep the outlet oil temperature or return
oil temperature at the setting temperature within
the range specified in the right column.
Mode 1
Outlet oil temperature or
return oil temperature control
Fixed temperature control
Outlet oil temperature or
return oil temperature control
Machine temperature
synchronous control
Oil temperature control
thermistor (When return oil
temperature is controlled)
5∼50℃
Keep the outlet oil temperature or return
oil temperature at the setting temperature within
the range specified in the right column.
Mode 5
Keep the outlet oil temperature or return
oil temperature at the setting temperature within
the range specified in the right column.
Mode 6
Oil temperature control
thermistor (When return oil
temperature is controlled)
Oil temperature control
thermistor (When return oil
temperature is controlled)
Machine temperature
synchronous thermistor
5∼50℃
Default setting: Set to“Mode: 3and temperature to“0.0. When you use your unit at a setting other than
the default setting, change the setting following the procedure shown below.
The following points can be checked in the monitor mode.
Points checked in the monitor mode
Monitor No. Description Note Monitor No. Description Note
The number of theMode”
is decreased by one.
The number of theMode”
is increased by one.
TheSetting temperature”
is reduced by 0.1.
TheSetting temperature”
is increased by 0.1.
Change the mode Change the setting temperature
3
4
Press the or key for mode setting.
Determine the value by pressing the key.
5
6
Press the
or
key for temperature setting.
Determine the value by pressing the key.
7 To return to the Normal” mode, press the key three times.
1 Power ON --- Release the operation lock mode before starting operation for the first time.
Hold down the key and key simultaneously for more than 5 seconds.
2 Select the “Setting mode and press the key once.
Blinking Blinking