4. Base Monitoring Unit
4.1 Functional Description
z Initialization: Power up the BMU and initialization operation follows.
The firmware version displays.
The 16 STATUS LED light red and green just one time.
Ever y LED displays from 0 to 9 in sequence.
B eep sounds two times.
z SENSOR_ID
Sensor ID automatically rotates 1, 2, 3, , 16 in sequence at 3 seconds intervals.
z GROUP ID
GROUP ID can be set among 1, 2, 3, , 16.
z TEMP/VOLT1/TEMP_HI LED
Shows the current temperature, voltage 1 and TEMP_HI value as per operating mode.
z HUMID/VOLT2/T EMP_LO LED
Shows the current humidity, voltage 2 and TEMP_LO value as per operating mode.
z 16 STATUS LED
When it detects the wireless r emote se nsing unit, LED lights green.
If it detects the abnormal temperature condition of WSU, LED blink in red at 1 second
intervals with beep sound.
If it fails to detect the WSU in pre-determined time 3 seconds, LED turns on red with beep
sound.
If it detects the low battery of WSU, LED blink in green at 1 second intervals, but no beep
sound.
z ALAM R ON/OFF Button
By pressing ALARM button, you can ON or OFF the alarm beep sound, which is noticed
with Green alar m LED.
The defaults alarm setting is ON with Green alar m LED ON.