GreenOK-II : Wireless Thermo-Hygro Monitor
User’s Manual (Rev 2.1)
-XX-
3.2 How to set the DIP Switch #1
DEVICE TYPE
ཛ The DEVICE T YPE can be configured as one of GMS-120ZB, GMS-130ZB and
GMS-140ZB as per the sensor connected.
ཛྷ The d efault TYP E is GMS-120ZB.
ཝ If the wrong DEVICE TYP E is configured, you may not read the correct data.
TX INTERVAL
ཛ The TX INTEVAL can be configured as 15sec or 1sec.
ཛྷ The d efault INTERVAL is 15 seconds.
<Figure 5> DIP Switch #1 Configuration of Wireless Sensing Unit
<IMPORTANT>
WHENEVER YOU CHANGE ANY DIP SWITCH
POSITION, YOU MUST REBOOT THE UNIT IN
ORDER TO MAKE THE CHANGE BE EFFECTIVE.