User`s guide

112 Chapter 5 Configuring the XStack Storage
Figure 5-47. Battery Policy Dialog Box
3. Select the appropriate setting that the XStack Storage unit should use if the battery fails. The
choices are:
Ignore the status of the battery and do nothing. Use this setting if you will be operating
the XStack Storage from AC power with an uninterruptible power supply.
Stop buffering I/O in cache, and directly write data to disk. Use this setting if you want
to write to disk all I/O buffered in cache memory in the event of a battery failure.
If the XStack Storage unit is operating from an uninterruptible power supply
(UPS) and the UPS fails, there may not be sufficient time to write all the
buffered I/O to disk. This can result In lost or unintelligible data.
Prevent any reads from or writes to volumes. This setting prevents all read and write
operations from occurring if the battery fails.
4. Click OK.