Specifications
SPECIFICATION
240W Single Output Industrial DIN RAIL
NDR-240 series
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE Note.4
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVER TEMPERATURE
SAFETY STANDARDS
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
AC CURRENT (Typ.)
1500ms, 100ms/230VAC 3000ms, 100ms/115VAC at full load
28ms/230VAC 22ms/115VAC at full load
90 ~ 264VAC 127 ~ 370VDC
47 ~ 63Hz
2.5A/115VAC 1.3A/230VAC
29 ~ 33V
88.5%
56 ~ 65V
90%
20A/115VAC 35A/230VAC
<1mA / 240VAC
Protection type : Shut down o/p voltage, re-power on to recover
Shut down o/p voltage, recovers automatically after temperature goes down
Ul508, TUV EN60950-1 approved
Compliance to EN55032 (CISPR32), EN61204-3 Class B, EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A
-20 ~ +70℃ (Refer to "Derating Curve")
20 ~ 95% RH non-condensing
-40 ~ +85℃, 10 ~ 95% RH
±0.03%/℃ (0 ~ 50℃)
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
230.2K hrs min. MIL-HDBK-217F (25℃)
63*125.2*113.5mm (W*H*D)
1Kg; 12pcs/13Kg/1.1CUFT
NDR-240-24 NDR-240-48
24V 48V
10A 5A
0 ~ 10A 0 ~ 5A
240W 240W
150mVp-p 150mVp-p
24 ~ 28V 48 ~ 55V
±1.0% ±1.0%
±0.5% ±0.5%
±1.0% ±1.0%
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH
ENVIRONMENT
SAFETY &
EMC
(Note 4)
PROTECTION
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE Note.3
℃
EMC IMMUNITY
EMC EMISSION
105 ~ 130% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
POWER FACTOR (Typ.) PF>0.98/115VAC, PF>0.95/230VAC at full load
;(meet EN60204-1)
File Name:NDR-240-SPEC 2017-07-07