Datasheet

www.cynergy3.com
© 2017 Cynergy3 Components, All Rights Reserved. Specifications are subject to change without prior notice. Cynergy3 Components and the Cynergy3 Components logo are trademarks of Cynergy3 Components Limited.
ISO
9001
CERTIFIED
Cynergy3 Components Ltd.
7 Cobham Road
Ferndown Industrial Estate
Wimborne, Dorset 21 7BH PE
SC2002ALM-HL 2017
Telephone +44 (0) 1202 897969
Email:sales@cynergy3.com
Made in the UK
SC2002ALM-HL
Dual Trip Amplifier
Wide Range of User Configurable Inputs
Isolated Input Stage
Setpoints Available as 0-10V, (0-100%) on terminals9&12
2 Setpoints with Configurable Trip Action & Fail-safe mode
D.C or A.C. Power Supply Options, See 4002-ALM for Mains Version
The SC2002ALM-HL trip amplifier can
accept a wide range of user configurable
inputs including 4-20mA, 0-20mA, 0-5V
and 0-10V. The unit can have up to two relay
outputs and each can operate as a high or a
low trip; alternatively latching operation
using both trip points can be configured.
The relay outputs are single pole change-
over relays with mains voltage rating. Each
trip can be configured so that the alarm
condition can be above or below setpoint.
The relays can be energised or de-energised
in the alarm condition, satisfying fail-safe
and non-fail-safe applications. In addition
the alarm LEDs can be selected to light
when the relay is either on or off. All these
options are user-configurable using
internal DIP switches. This minimises the
number of spare units required.
The input stage is fully isolated and the
high level input current or voltage and
range may be configured. Separate
products are available for thermocouple
and RTD inputs.
Inputs
SC-2002ALM-HL Standard Ranges
0-20mA, 4-20mA, 0-10mA into 12 /15 /24
ΩΩΩ
0-5V, 0-10V into 1MΩ
Min and Max Full Scale Ranges available to order:
DC Current 0 to 1mA 0 to 5A
DC Voltage 0 to 100mV 0 to 300V
Note: For input voltages greater than 60Vdc a
Divider unit must be specified.
Outputs
Mains Rated Relays - 3A resistive at 240V ac
Technical Specifications
Parameter Min Typ Max Comments
Supply Voltage 24V
Supply Current (mA) 45
24Vdc supply, both relays energised
Volt Drop (mA input) 0.3 0.35 At 20mA Input
Input Impedance (Volt) 100k 1M 10M Dependant on range (typ=10V)
ΩΩ Ω
Input Impedance (mA) 0.02 15 5k Dependant on range (typ=4-20mA)ΩΩ Ω
Trip Point Accuracy 0.25%
Trip Point Drift ±100ppm/ºC
Temp Coefficient ±100ppm/ºC
Hysteresis 1% span
Time Constant (10-90%) 10ms
Operating Ambient 0ºC 55ºC
Relative Humidity 0% 90%
Isolation Voltage 1kV
see note
Surge Voltage 2.5kV for 50µS Transient of 10kV/µS
Notes
Setpoints are adjusted by 20 turn potentiometers on the front panel.
Setpoints can be checked by measuring the 0-10V (0-100%) voltage on terminals 9 &12
H/H,H/L, L/H, LL, fail-safe, non-fail safe and LED options are user selectable using internal links.
Hysteresis is set at 1.0% but other values are possible, please specify if required.
Installation Data
Mounting DIN Rail TS35
Orientation Any
Connections Screw Clamp with pressure plate
Conductor Size 0.5-4.0mm
Insulation Stripping 12mm
Weight Approx 120g
Ordering Information
Part No.: SC2002ALM-HL
Connection Details
10. Power input -ve
11. Power input +ve
7. Process Input -ve and Setpoint common
8. Process input +ve
9. Setpoint 1 (0-10V = 0-100%)
12. Setpoint 2 (0-10V = 0-100%)
1. Relay 1 Common 4. Relay 2 Common
2. Relay 1 N/C 5. Relay 2 N/C
3 . Relay 1 N/O 6. Relay 2 N/O

Summary of content (1 pages)