SC-DUALCON3
Isolating Signal Converter - 2 Outputs
90-264Vac power supply
Selectable mA or Voltage output
Isolated Transmitter Supply
Very High Accuracy, Low Cost
Only 17.5mm Wide on DIN rail
Universal Configurable Input
2 Configurable Outputs, full 3-port isolation
The SC-DUALCON3 Isolating Signal
Converter can accept a wide range of
inputs including 4-20mA, thermocouple,
RTD and voltage signals. The units produce
two high level DC outputs of either voltage
or current.
Full 3 port isolation is standard as is an
isolated transmitter supply which can be
used to power any standard 2-wire
4-20mA transmitter.
The input type and range can be user
selected using simple DIL switches inside
the unit. All RTD and Thermocouple inputs
can be fully linearised.
Non-interactive zero and span controls
make adjustment of the unit quick and
simple.
Other features include optional inversion of
the input signal, on either one or both of the
outputs
The unit operates from any supply from 90
to 264 Vac
For specials such as averaging of the input
signal, custom linearisation etc please
contact the sales office.
Inputs
DC/AC Current & Voltage
0-20mA, 4-20mA, 0-10mA into 15
Ω
0-1V, 0-10V, 1-5V into 1MΩ
Min & Max Full Scale Ranges are:
* Note: For input voltages greater than 60Vdc a Divider unit must be specified.
Thermocouples
Types E,J,K,N,R,S,T,B linearised or non-linearised. Ranges: Wide range of inputs. Cold junction compensation
(can be turned off). Upscale or downscale t/c burnout options
Resistance Thermometers
2, 3 or 4 wire PT100 or PT1000, linearised or non-linearised. Ranges: Wide range of inputs.
Upscale or downscale RTD burnout options.
Technical Specifications
Parameter Min Typ Max Comments
Supply Voltage (Vac) 90 264 50 or 60 Hz
VA Rating 4.7VA±10% 20mA in & out & transmitter supply
Volt Drop (mA input) 0.3 At 20mA Input
Input Impedance (Volt) 1M 100M Dependant on range (typ=10V)
ΩΩ
Input Impedance (mA) 15 Dependant on range (typ=20mA)Ω
Output Linearity Error ±0.01% 0.05%±
Temp Coefficient ±50ppm/ºC
Load Resistance Error ±5ppm/ 0 < RL < 750
ΩΩ
Time Constant (10-90%) 25mS 60mS Selectable fast/normal response
Operating Ambient 0ºC 55ºC
Relative Humidity 0% 90%
Isolation Voltage 1kV
see note
Surge Voltage 2.5kV for 50µS Transient of 10kV/µS
Notes
Absolute maximum ratings indicate sustained limits beyond which damage to the device may occur.
Device is protected against reverse polarity connection.
Accuracy figures based on 110Vac supply, 2 x 4-20mA outputs with 250 load and an ambient 20ºC.
Ω
SC-DUALCON3 does NOT provide safety isolation when the input is connected to the mains.
Installation Data
Mounting DIN Rail TS35
Orientation Any
Connections Screw Clamp with pressure plate
Conductor Size 0.5-4.0mm
Insulation Stripping 12mm
Weight Approx 115g
Ordering Information
Part No.: SC-DUALCON3
DC Current 0 - 1mA 0 - 5A
Bipolar DC Current ±5mA ±10mA
DC Voltage 0 - 1V 0 - 300V*
Bipolar DC Voltage ±5V ±10V
2 Wire Pot 0 - 125Ω 0 - 1kΩ
3 Wire Pot 0 - 1kΩ 0 - 100kΩ
Outputs
DC Current and Voltage
0-20mA, 4-20mA, 0-10mA into 750
Ω
0-1V, 0-10V, 1-5V into a minimum 100kΩ
Others available up to a maximum of:
Current: 0-20mA. Voltage: 0-20Vdc
Connection Details
1. Power supply -ve
2. Power supply +ve
4. Process Input -ve T/C -ve RTD -ve
5. Process Input +ve T/C +ve RTD +ve
3. Trans supply +ve RTD 4 wire
th
6. T/C Shield RTD 3 wire
rd
10. Output 2 -ve 7. Output 1 -ve
12. Output 2 +ve 9. Output 1 +ve