Cyclades® PM IPDU Installer/Administrator/User Guide For Technical Support: www.avocent.com/support Avocent Corporation 4991 Corporate Drive Huntsville, Alabama 35805-6201 USA Tel: +1 256 430 4000 Fax: +1 256 430 4031 Avocent International Ltd.
FCC Warning Statement The Cyclades PM IPDU has been tested and found to comply with the limits for Class A digital devices, pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.
Cyclades® PM IPDU Installer/Administrator/User Guide Avocent, the Avocent logo, The Power of Being There and Cyclades are registered trademarks of Avocent Corporation. All other marks are the property of their respective owners. © 2006 Avocent Corporation. All rights reserved.
Instructions This symbol is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in the literature accompanying the appliance. Dangerous Voltage This symbol is intended to alert the user to the presence of uninsulated dangerous voltage within the product’s enclosure that may be of sufficient magnitude to constitute a risk of electric shock to persons. Power On This symbol indicates the principal on/off switch is in the on position.
iii TABL E OF CONTEN TS Table of Contents List of Figures ................................................................................................................ vii List of Tables ................................................................................................................... ix Chapter 1: Introduction ................................................................................................... 1 Features and Benefits .....................................................
iv Cyclades PM IPDU Installer/Administrator/User Guide Supplied with the PM IPDU ............................................................................................................ 13 Modular input power cables for the PM IPDU ........................................................................ 14 Optional outlet cable package .................................................................................................. 16 Rack Mounting the Cyclades PM IPDU ...............................
Table of Contents v hwocp ............................................................................................................................................... 44 id ...................................................................................................................................................... 45 interval ............................................................................................................................................. 46 list......................
vi Cyclades PM IPDU Installer/Administrator/User Guide
vii L IS T O F F IG URE S List of Figures Figure 1.1: Standalone Configuration............................................................................................... 3 Figure 1.2: Daisy Chained Configuration......................................................................................... 4 Figure 1.3: The Cyclades PM IPDU with a Cyclades Management Device..................................... 5 Figure 1.4: Cyclades PM8 IPDU ...................................................................
viii Cyclades PM IPDU Installer/Administrator/User Guide
ix L I S T OF T A B L ES List of Tables Table 2.1: PM IPDU Shipping Box Contents, Part Numbers and Description............................... 13 Table 2.2: PM8i-10A IPDU and PM10i-10A IPDU Power Cables ................................................ 15 Table 2.3: PM10i-15A IPDU Power Cables ................................................................................... 16 Table 2.4: PM10i-16A IPDU and PM 20i-16A IPDU Power Cables ............................................. 16 Table 2.
x Cyclades PM IPDU Installer/Administrator/User Guide Table A.19: Pinouts for IN and OUT RS-232 Serial Ports.............................................................. 72 Table C.1: Circuit Breaker Trip Time .............................................................................................
1 CHA PTER 1 Introduction This installation, administration and user’s guide provides background information and procedures for installing, configuring and maintaining the Cyclades® Power Management (PM) Intelligent Power Distribution Unit (IPDU) family. This guide offers procedures for a stand-alone configuration. If you are integrating your PM IPDU with a Cyclades KVM or console management device, please see the related installation instructions for that product.
2 Cyclades PM IPDU Installer/Administrator/User Guide Support for daisy chaining The IPDU has a fixed number of power outlet receptacles, but with daisy chaining capabilities, users may increase capacity by connecting the control interfaces of several Cyclades PM IPDUs in a series. Creation of user accounts The Cyclades PM IPDU allows one administrator and up to eight users (not simultaneously) to connect to it through its RS-232 serial port.
Chapter 1: Introduction RJ-45 to DB-9F Adaptor 3 RJ-45 Cable Power Source User IN Port Server Switch Figure 1.1: Standalone Configuration NOTE: The previous graphic displays the PM IPDU being connected to the local work station with the RJ-45 to DB-9F adaptor that is shipped with the product. If your work station does not have a DB-9M COM port, you may need to use a USB serial adaptor in order to connect to the computer’s USB port.
4 Cyclades PM IPDU Installer/Administrator/User Guide RJ-45 to DB-9F Adaptor RJ-45 Cable Power Source User IN Port PM IPDU #1 PM IPDU #2 OUT Port PM IPDU #3 PM IPDU #4 Additional Cyclades PM IPDUs with up to a total of 128 outlets can be daisy-chained Server Switch Figure 1.2: Daisy Chained Configuration NOTE: The previous graphic displays the PM IPDU being connected to the local work station with the RJ-45 to DB-9F adaptor that is shipped with the product.
Chapter 1: Introduction 5 itself. Visit http://www.cyclades.com/support/downloads.php to find setup and configuration instructions for the Cyclades management products. Power Source PM IPDU #1 AlterPath OnSite PM IPDU #2 PM IPDU #3 PM IPDU #4 Additional Cyclades PM IPDUs with up to a total of 128 outlets can be daisy-chained Server Switch Figure 1.
6 Cyclades PM IPDU Installer/Administrator/User Guide however, in the integrated configuration, the first Cyclades PM IPDU is connected to a Cyclades management device instead of a workstation. Accessing the System Console Users and administrators may access the Cyclades PM IPDU either by making a direct console connection to the PM IPDU’s IN port or by connecting the PM IPDU to a Cyclades console or KVM switch management device.
Chapter 1: Introduction Component Overview General features are common among all products, in the Cyclades PM IPDU family: • 128 KB flash memory • 8 KB RAM • Two RJ-45 RS-232 interfaces • Digital global current display with two digits and seven segments • LEDs monitoring ON/OFF status for each port • Audible over current alarm • 8-bit Microcontroller-equipped The following sections list features that are specific to each model: • Cyclades PM8 IPDU on page 7 • Cyclades PM8i IPDU on page 8
8 Cyclades PM IPDU Installer/Administrator/User Guide Cyclades PM8i IPDU The Cyclades PM8i IPDU has the following features: • One 240VAC/8A power inlet (IEC320-C14). See PM8i-10A IPDU and PM10i-10A IPDU power cables on page 15 for a list of which power cables are supplied by region. • Eight 240VAC/8A power receptacles (IEC320-C13) • 240VAC/10A supplementary protector • Horizontal (1.5U) mounting Power Outlets (IEC320-C13) OUT Port IN Port Power Inlet Digital Current Display Figure 1.
Chapter 1: Introduction Cyclades PM10i IPDU The Cyclades PM10i IPDU has the following features: • One of the following power plugs: • 240VAC/10A power plug (IEC320-C14) • 240VAC/16A power plug (IEC320-C20) • Ten 240VAC/10A power receptacles (IEC320-C13) • 240VAC/10A/20A supplementary protector • Horizontal (1U) mounting 10 IEC320-C13 Power Outlets IN Port IEC320-C14 Power Inlet OUT Port Figure 1.7: Back of the Cyclades PM10iIPDU Power Outlet LEDs Digital Current Display Figure 1.
10 Cyclades PM IPDU Installer/Administrator/User Guide • Horizontal (1U) mounting Refer to Figure 1.7 on page 9 and Figure 1.8 on page 9 for images of the Cyclades PM10i-32A IPDU. Cyclades PM10i-32Au IPDU The Cyclades PM10i-32Au IPDU has the following features: • 32A unterminated input power cord • Ten 240VAC/10A power receptacles (IEC320-C13) • Two 240VAC/16A magnetic circuit breakers with accidental-off protection function • Horizontal (1U) mounting Refer to Figure 1.7 on page 9 and Figure 1.
Chapter 1: Introduction • Vertical mounting (zero U) Figure 1.10: The Cyclades PM20i IPDU, PM20i-32A IPDU and PM20i-32AU IPDU Cyclades PM20i-32A IPDU The Cyclades PM20i-32A IPDU has the following features: • 32A input power cord; IEC 309 plug. • Twenty 240VAC/10A power receptacles (IEC320-C13) • 240VAC/two 16A magnetic circuit breakers with accidental-off protection function • Vertical mounting (zero U) Refer to Figure 1.10 on page 11 for an image of the Cyclades PM20i-32A IPDU.
12 Cyclades PM IPDU Installer/Administrator/User Guide
13 CHA PTER Installation 2 Getting Started Collect the following equipment prior to installing and configuring the Cyclades PM IPDU in standalone configuration: • One or more RJ-45 to RJ-45 straight-through cables • An RJ-45 to DB-9F straight-through adaptor • A PC running a terminal emulation program See the following section for the list of other necessary items that come with the PM IPDU.
14 Cyclades PM IPDU Installer/Administrator/User Guide Table 2.1: PM IPDU Shipping Box Contents, Part Numbers and Description (Continued) P/N Description Purpose CON0132 RJ-45 loopback connector In case the administrator forgets the admin's password, this is used to place in the OUT port to gain temporary access to the box using the factory default password. See To reset the admin password using the loopback connector: on page 25.
Chapter 2: Installation PM8i-10A IPDU and PM10i-10A IPDU power cables Table 2.
16 Cyclades PM IPDU Installer/Administrator/User Guide PM10i-15A IPDU power cables Table 2.3: PM10i-15A IPDU Power Cables P/N Country/Region CAB0191 US PM10i-16A IPDU and PM 20i-16A IPDU power cables Table 2.4: PM10i-16A IPDU and PM 20i-16A IPDU Power Cables P/N Country/Region CAB0193 Continental Europe CAB0192 Australia and New Zealand CAB0194 United Kingdom and Ireland (fuse limited to 13A as per BS1363) PM10i-20A IPDU and PM 20i-20A IPDU power cables Table 2.
Chapter 2: Installation • 17 If you are mounting the PM IPDU, obtain a Phillips screwdriver and appropriate nuts and bolts before starting the following procedure. NOTE: When mounting a Cyclades PM IPDU zero U model to a wall stud, securely mount it by using a #10 or larger screw or use a drywall fastener rated min. 25 lb. (11.34 kg). The following graphics depict the orientation of the brackets for front rack mounting PM IPDU. Bracket Figure 2.
18 Cyclades PM IPDU Installer/Administrator/User Guide Table 2.6: PM IPDU Optimum Installation Environment (Continued) Environment Factor Recommendation Reliable Grounding Reliable grounding of rack-mounted equipment should be maintained. Particular attention should be given to supply connections other than direct connections to the branch circuit, such as power strips or extension cords.
Chapter 2: Installation 19 NOTE: The suggested minimum screw size for wall-mounting the Cyclades PM IPDUs is #10 (4.8 mm or 0.19 in or 3/16 in) or larger. The RJ-45 cable included in the Cyclades PM IPDU package is minimum flame rated VW-1 or FT-1 and has a maximum length of 10 feet (3 meters). Nodes PM8i IPDU, PM10 IPDU or PM10i IPDU Cyclades ACS Console Server, Cyclades TS Terminal Server, Cyclades KVM Switch or Cyclades OnSite Appliance Switch Router Ethernet PBX UPS UNIX server Figure 2.
20 Cyclades PM IPDU Installer/Administrator/User Guide 3. To connect another PM IPDU to the slave, connect one end of an RJ-45 cable to the OUT port of the last PM IPDU in the chain. 4. Repeat Step 3 until you have connected the desired number of PM IPDUs. You may control up to 128 power outlets in any combination of PM IPDU models. Plugging Devices Into PM IPDU Outlets In order to control power to a device, the device must be plugged into one of the PM IPDU’s power outlets.
Chapter 2: Installation RJ-45 to DB-9F 21 Local Workstation RJ-45 Cable Cyclades PM IPDU IN Port Figure 2.5: Connecting a Local Work Station to the Cyclades PM IPDU To access the console: Perform the following steps to connect a computer to the console port of the PM IPDU. This procedure assumes that you know how to use a terminal emulation program. On a PC, ensure that HyperTerminal or another terminal emulation program is installed on the Windows operating system.
22 Cyclades PM IPDU Installer/Administrator/User Guide To log into the PM IPDU through the console (IN port): From your terminal emulation application, log into the console port as admin. AlterPath PM Copyright (c) 2002-2006 Avocent Corporation V 1.9.0 Jun 21, 2006 [PM]: IPDU: 1 [PM]: OUT: 10 Username: admin The default password is pm8. If the password has been changed from the default, use the new password.
23 CHA PTER 3 Configuration The Cyclades PM IPDU may be configured by any one of three methods: • Command Prompt - Full configuration capabilities. • Browser - Available only when the PM IPDU is connected directly to an AUX port on a KVM switch or OnSite appliance or connected directly to a serial console port on an ACS console server, TS terminal server or OnSite appliance.
24 Cyclades PM IPDU Installer/Administrator/User Guide Initial Configuration Using the Command Prompt To configure the PM IPDU, you must have a work station connected to the console (In) port on the PM IPDU and be logged in as the admin user. See Making a Direct Connection for Console Access on page 20 for instructions on connecting to the console. If needed, refer to Chapter 4 beginning on page 31. To change the default password: If the default pm8 password is still in use, change the admin password.
Chapter 3: Configuration 25 To save the configuration with the save command: 1. Login to the PM IPDU. 2. Enter the save command to save the configuration. Resetting the Admin Password In the event the administrator wants to reset the password for the Cyclades PM IPDU (for example, if the administrator forgets the admin password), then the loopback connector that is shipped with the Cyclades PM IPDU may be used for temporary access to the PM IPDU.
26 Cyclades PM IPDU Installer/Administrator/User Guide 7. If you need to recover the password of many Cyclades PM IPDUs connected in a daisy chain, go to step 1 and perform the procedure on each Cyclades PM IPDU in the chain. Upgrading the Cyclades PM IPDU Firmware Starting with version 1.1.0, the Cyclades PM IPDU firmware may be upgraded through its IN port. The upgrade procedure described here is only valid for units that are currently running firmware versions 1.3.0 or greater.
Chapter 3: Configuration 27 After the upgrade command is executed, the boot loader menu is displayed at the console, as shown below: pm>upgrade 1 ----------------------------Copyright (c) 2003 Cyclades Corporation AlterPath PM/KVM Boot Loader Version 1.1 ----------------------------Boot Menu 1. Upgrade Firmware. 2. Boot Firmware. ----------------------------Enter choice (1 or 2): 1 3. At the boot loader menu, select option 1 to upgrade the firmware.
28 Cyclades PM IPDU Installer/Administrator/User Guide Figure 3.1: Sending Firmware using HyperTerminal 2. Click the Browse button to set the proper path for the Cyclades PM IPDU firmware file located on your work station. NOTE: You must browse for the proper file and click the Send button within 10 seconds of selecting Transfer-Send. If you fail to do so, an error message will appear and the transmission will fail. You will then be given another 10-second window in which to repeat steps 1. through 4.
Chapter 3: Configuration 29 Figure 3.2: Sending Firmware using Minicom If you use a different terminal emulator, please refer to the documentation provided by the manufacturer on how to transfer files using the xmodem protocol. If the file transfer is successful, the Cyclades PM IPDU console displays the login prompt. At this point, the upgrade process of the unit is complete; you may log into the Cyclades PM IPDU and perform actions as usual.
30 Cyclades PM IPDU Installer/Administrator/User Guide In this case, select option 2 from the menu and repeat the firmware upload procedure. If the problem persists, contact Technical Support for assistance.
31 CHA PTER 4 Command Line Interface When using the Cyclades PM IPDU independently of other Cyclades products, users and administrators may access the PM IPDU command line interface through a terminal emulation program by making a console connection from a local computer to the IN port on the PM IPDU. See To access the console: on page 21 for instructions. PM IPDU User Interface You may access the PM IPDU user interface by following the instructions provided in To access the console: on page 21.
32 Cyclades PM IPDU Installer/Administrator/User Guide Logging in to the PM IPDU After the Username: prompt, enter your username. NOTE: If there are daisy chained PM IPDUs, you will need to press Enter after the final [PM]: OUT: line appears. After the Password: prompt, enter the password for the unsername entered. The default user is admin and the default password is pm8. After a successful login, the PM IPDU command prompt appears after which you may use any of the commands described in this chapter.
Chapter 4: Command Line Interface 33 The following commands are available only to the admin user. Table 4.
34 Cyclades PM IPDU Installer/Administrator/User Guide alarm The alarm command sets and reads the current threshold. This command is available to the admin user only. Syntax alarm | [|] | Arguments IPDU number in a daisy chain Identification string previously set by the id command.
Chapter 4: Command Line Interface 35 Examples To assign outlet 4, 6, 7, and 8 to user tess, enter the following. pm>assign 4: Outlet 6: Outlet 7: Outlet 8: Outlet 4, 6-8 tess assigned to assigned to assigned to assigned to tess. tess. tess. tess. buzzer The buzzer command displays or changes the buzzer notification status. When set to on, a buzzer sounds when the current exceeds the threshold. This command is available to the admin user only.
36 Cyclades PM IPDU Installer/Administrator/User Guide Syntax current [|]|reset Arguments IPDU number in a daisy chain Identification string previously set by the id command reset Clears the saved peak current value Examples To get the current status for all units, enter the following. pm> current IPDU #1: True RMS current: 2.2A. Maximum current: 9.4A IPDU #2: True RMS current: 2.0A. Maximum current: 10.
Chapter 4: Command Line Interface Examples To display current protection status for all units, enter the following. pm>currentprotection status IPDU #1: Overcurrent protection is OFF. IPDU #2: Overcurrent protection is OFF. To enable current protection status for all units, enter the following. pm>currentprotection ON IPDU #1: Overcurrent protection turned ON. IPDU #2: Overcurrent protection turned ON. To disable current protection status for all units, enter the following.
38 Cyclades PM IPDU Installer/Administrator/User Guide To view the current load of segment B, enter the following. pm>currseg B IPDU #1: True RMS current for segment B: 2.5A. Maximum current for segment B: 2. 5A To reset the maximum recorded current for A and B, enter the following. pm>currseg reset IPDU #1: Clearing maximum recorded current for segment A and B to zero. cycle The cycle command power cycles an outlet or groups of outlets.
Chapter 4: Command Line Interface 39 To cycle multiple outlets, enter the following. pm>cycle 2, 3, 5-7 2: Outlet turned off. 3: Outlet turned off. 5: Outlet turned off. 6: Outlet turned off. 7: Outlet turned off. 2: Outlet turned on. 3: Outlet turned on. 5: Outlet turned on. 6: Outlet turned on. 7: Outlet turned on. dbsync The dbsync command synchronizes the user database for all PM IPDUs in the chain. This command is available to the admin user only.
40 Cyclades PM IPDU Installer/Administrator/User Guide Examples To delete the user rog, enter the following. pm>deluser rog Username deleted. display The display command allows logical inversion of the 2-digit, 7-segment display. The purpose of this command is to allow a PM IPDU to be mounted upside-down. This command is available to the admin user only. NOTE: The decimal point will be at the top of the display when the PM IPDU is mounted upside down.
Chapter 4: Command Line Interface 41 To view the display status, enter the following. pm>display IPDU #1: Display mode set to normal. IPDU #2: Display mode set to 180 degrees rotated. IPDU #3: Display mode set to show current and cycle each 2 seconds. exit The exit command exits the session. Syntax exit Arguments none Examples To exit the current session, enter the following. pm>exit AlterPath PM Copyright (c) 2002-2006 Avocent Corporation V 1.9.
42 Cyclades PM IPDU Installer/Administrator/User Guide Examples To reset the factory defaults, enter the following. pm>factory_defaults 1 Setting configuration to defaults on IPDU #1 1: Outlet turned on. 2: Outlet turned on. 3: Outlet turned on. 4: Outlet turned on. 5: Outlet turned on. 6: Outlet turned on. 7: Outlet turned on. 8: Outlet turned on. Saving configuration to flash on IPDU #1 ... done.
Chapter 4: Command Line Interface 43 To view the system help message for all commands, enter the following.
44 Cyclades PM IPDU Installer/Administrator/User Guide Arguments IPDU number in a daisy chain Identification string previously set by the id command reset Resets the maximum humidity registered Examples To get the humidity for all units in a daisy chain, enter the following. pm> humidity IPDU #1: humidity: 42.3%. Maximum: 58.7% IPDU #2: humidity: 44.0% Maximum: 72.6% IPDU #3: Does not have humidity sensor.
Chapter 4: Command Line Interface 45 Examples To check the hardware overcurrent status of IPDU #1, enter the following. pm>hwocp 1 IPDU #1: HW overcurrent protection is OFF. To reset the hardware overcurrent protection, enter the following. pm>hwocp 1 reset IPDU #1 was reset id The id command sets or displays the ID of a PM IPDU. A maximum of 16 characters (not case sensitive) is allowed. Spaces, numbers, and special characters are allowed. This command is available to the administrator user only.
46 Cyclades PM IPDU Installer/Administrator/User Guide To display the ID of PM IPDU 2, enter the following. pm>id 2 IPDU #2: id = QA To rename an ID to “sammy,” using an existing ID “QA,” enter the following. pm>id QA sammy IPDU #2 = sammy To display the IDs of all PM IPDUs in the daisy chain, enter the following. pm>id IPDU #1: id = R&D IPDU #2: id = QA interval The interval command configures the power up interval for each outlet in the system.
Chapter 4: Command Line Interface To set the interval of outlets 2, 4, 5, and 6 to a value of 2.4, enter the following. pm>interval 2,4-6 2.4 2: Outlet power on interval 4: Outlet power on interval 5: Outlet power on interval 6: Outlet power on interval set set set set to to to to 2.4 2.4 2.4 2.4 sec. sec. sec. sec.
48 Cyclades PM IPDU Installer/Administrator/User Guide lock The lock command locks an outlet or group of outlets in the current state. The response to this command is a list of status lines, one per power port. This command works on all PM IPDUs in a daisy chain. Syntax lock all| Arguments Outlet number, such as “5”, outlet name such as “sunfire”, or group of outlets such as “1, 3-5” Examples To lock outlets 1, 2, and 6, enter the following. pm>lock 1,2,6 1: Outlet locked.
Chapter 4: Command Line Interface 49 off The off command turns an outlet or group of outlets off. This command works on outlets in a PM IPDU daisy chain. Syntax off all| Arguments all Turns off all outlets in the PM IPDU or PM IPDU daisy chain Outlet number, such as “5”, outlet name such as “sunfire”, or group of outlets such as “1, 3-5” CAUTION: The “all” argument will turn off all outlets in a PM IPDU or PM IPDU daisy chain.
50 Cyclades PM IPDU Installer/Administrator/User Guide on The on command turns an outlet or a group of outlets on. If more than one outlet is selected there will be an interval between outlets being powered on, the interval is defined by the interval command. This command works on outlets in a PM IPDU daisy chain.
Chapter 4: Command Line Interface 51 Examples To change the password for user alpha, when logged in as admin, enter the following. pm>passwd alpha Password: Re-enter password: Username/password set for user alpha. To change the admin password (must be logged in as admin), enter the following pm>passwd Password: Re-enter password: Username/password set for user admin. To change the password of a regular user when logged in as that user, enter the following.
52 Cyclades PM IPDU Installer/Administrator/User Guide Examples To reboot the first unit of the chain, or to reboot the unit in stand alone mode, enter the following. pm>reboot saving configuration to flash on IPDU #1 ... Done. ----------------------------Copyright (c) 2003 Cyclades Corporation AlterPath PM/KVM Boot Loader Version 1.1 ----------------------------Boot Menu 1. Upgrade Firmware. 2. Boot Firmware. ----------------------------Enter choice (1 or 2): Timeout... Booting... V_1.6.
Chapter 4: Command Line Interface 53 restore The restore command restores the configuration currently saved in flash. This command is available to the admin user only. Syntax restore Arguments N/A Examples To restore the configuration currently saved in flash, enter the following. pm>restore 1: Outlet turned 2: Outlet turned 3: Outlet turned 4: Outlet turned 5: Outlet turned 6: Outlet turned 7: Outlet turned 8: Outlet turned on. on. on. on. on. on. on. on.
54 Cyclades PM IPDU Installer/Administrator/User Guide Examples To save the configuration to flash, enter the following. pm>save Saving configuration to flash on IPDU #1 ... Done. Saving configuration to flash on IPDU #2 ... Done. An error message will be displayed if there is an error while writing the configuration to flash. status The status command displays the status of selected outlets.
Chapter 4: Command Line Interface 55 To display the status of all outlets, enter the following. pm>status all Outlet Name 1 g1 2 g2 3 g3 4 g4 ON 2.40 5 g5 ON 2.40 6 g6 ON 2.40 7 g7 ON 0.50 8 g8 ON 0.50 Status Unlocked ON Unlocked ON Unlocked ON Unlocked george, sarah Unlocked mila, sarah Unlocked george, sarah Unlocked george, sarah Unlocked mila, sarah Interval (s) 0.00 2.40 0.00 Users gregg gregg gregg syslog The syslog command displays or changes the syslog notification status.
56 Cyclades PM IPDU Installer/Administrator/User Guide To turn on and off the syslog notification, enter the following as necessary. pm>syslog on Syslog turned Syslog turned pm>syslog off Syslog turned Syslog turned ON on IPDU #1 ON on IPDU #2 OFF on IPDU #1 OFF on IPDU #2 temperature The temperature command displays the Cyclades PM IPDU’s surrounding temperature and the maximum temperature the unit has registered (temperature peak). It may also be used to clear the saved peak temperature value.
Chapter 4: Command Line Interface 57 unassign The unassign command removes the assignment of an outlet or group of outlets from a given user. This command is available to the admin user only. Syntax unassign Arguments Outlet number, such as “5”, outlet name such as “sunfire”, or group of outlets such as “1, 3-5” Desired username Examples To unassign outlet 2 and 4 from user diderot, enter the following.
58 Cyclades PM IPDU Installer/Administrator/User Guide upgrade The upgrade command is available only to the administrator. This command goes directly to the boot options menu before actually rebooting. You may either upgrade or boot the firmware. NOTE: For details on upgrading using the upgrade command or using the reboot command, see Upgrading the Cyclades PM IPDU Firmware on page 26.
Chapter 4: Command Line Interface Examples To upgrade 1, type: pm>upgrade 1 saving configuration to flash on IPDU #1 ... Done. ----------------------------Copyright (c) 2003 Cyclades Corporation AlterPath PM/KVM Boot Loader Version 1.1 ----------------------------Boot Menu 1. Upgrade Firmware. 2. Boot Firmware. ----------------------------Enter choice (1 or 2): 1 Erasing firmware...done. Downloading image. Please send file in 10 seconds.done. V_1.6.0 - compatible Saving configuration to flash on IPDU #1 ..
60 Cyclades PM IPDU Installer/Administrator/User Guide Arguments IPDU number in a daisy chain Identification string previously set by the id command no argument Displays version information for the PM IPDU and for all PM IPDUs in a daisy chain Examples To view the current software version of all IPDUs in a daisy chain, enter the following. pm>ver IPDU #1: Hw with 10 outlets 16 AMPs max Sw V 1.9.0 Jun 21, 2006 id mila model 7 IPDU #2: Hw with 8 outlets 15 AMPs max Sw V 1.9.
Chapter 4: Command Line Interface AB|AC|BC reserved for future use no argument displays the RMS voltage on all units if voltage sensors are available Examples whoami The whoami command shows the username of the user currently logged in. Syntax whoami Arguments none Examples To view the current username, enter the following.
62 Cyclades PM IPDU Installer/Administrator/User Guide
63 A P P EN D IC ES Appendices Appendix A: Specifications Table A.1: PM8-15A IPDU Specifications Characteristics Specifications Electrical Input Voltage 100-125 VAC Max Output Current Total 15A (de-rated to 12A) Max Output Current Each Outlet 15A (de-rated to 12A) Environmental Operating Temperature 50-122 ºF (10-50 ºC) Relative Humidity 5%-95% Mechanical Weight 6.1 lb (2.8 kg) Physical Dimensions (W x D x H) 1.8 x 2.2 x 37.6 in (4.57 x 5.6 x 95.
64 Cyclades PM IPDU Installer/Administrator/User Guide Table A.2: PM8-20A IPDU and PM8-L20A IPDU Specifications Characteristics Specifications Electrical Input Voltage 100-125 VAC Max Output Current Total 20A (de-rated to 16A) Max Output Current Each Outlet 15A (de-rated to 12A) Environmental Operating Temperature 50-122 ºF (10-50 ºC) Relative Humidity 5%-95% Mechanical Weight 6.1 lb (2.8 kg) Physical Dimensions (W x D x H) 1.8 x 2.2 x 37.6 in (4.57 x 5.6 x 95.5 cm) Table A.
Appendices Table A.4: PM10-15A IPDU Specifications Characteristics Specifications Electrical Input Voltage 100-125 VAC Max Output Current Total 15A (de-rated to 12A) Environmental Max Output Current Each Outlet 15A (de-rated to 12A) Operating Temperature 50-122 ºF (10-50 ºC) Relative Humidity 5%-95% Mechanical Weight 8 lb. (3.64 kg) Physical Dimensions (W x D x H) 17 x 8 x 1.75 in (43.18x 20.32 x 4.45 cm) Table A.
66 Cyclades PM IPDU Installer/Administrator/User Guide Table A.6: PM10-L30A IPDU Specifications Characteristics Specifications Electrical Input Voltage 100-125 VAC Max Output Current Total 30A (de-rated to 24A) Max Output Current Each Outlet 15A (de-rated to 12A) Environmental Operating Temperature 50-122 ºF (10-50 ºC) Relative Humidity 5%-95% Mechanical Weight 8 lb. (3.64 kg) Physical Dimensions (W x D x H) 17 x 8 x 1.75 in (43.18x 20.32 x 4.45 cm) Table A.
Appendices Table A.8: PM10i-15A IPDU Specifications Characteristics Specifications Electrical Input Voltage 100-240 VAC Max Output Current Total 15A (de-rated to 12A) Max Output Current Each Outlet 10A (de-rated to 8A) Environmental Operating Temperature 50-122 ºF (10-50 ºC) Relative Humidity 5%-95% Mechanical Weight 8 lb. (3.64 kg) Physical Dimensions (W x D x H) 17 x 8 x 1.75 in (43.18x 20.32 x 4.45 cm) Table A.
68 Cyclades PM IPDU Installer/Administrator/User Guide Table A.10: PM10i-20A IPDU Specifications Characteristics Specifications Electrical Input Voltage 100-240 VAC Max Output Current Total 20A (de-rated to 16A) Max Output Current Each Outlet 10A (de-rated to 8A) Environmental Operating Temperature 50-122 ºF (10-50 ºC) Relative Humidity 5%-95% Mechanical Weight 8 lb. (3.64 kg) Physical Dimensions (W x D x H) 17 x 8 x 1.75 in (43.18x 20.32 x 4.45 cm) Table A.
Appendices Table A.12: PM10i-L30A IPDU Specifications Characteristics Specifications Electrical Input Voltage 100-240 VAC Max Output Current Total 30A (de-rated to 24A) Max Output Current Each Outlet 10A (de-rated to 8A) Environmental Operating Temperature 32-122 ºF (0-50 ºC) Relative Humidity 5%-95% Mechanical Weight 12 lb. (5.45 kg) Physical Dimensions (W x D x H) 17 x 11.5 x 1.75 in (43.18x 29.21 x 4.45 cm) Table A.
70 Cyclades PM IPDU Installer/Administrator/User Guide Table A.14: PM20-L30A IPDU Specifications Characteristics Specifications Electrical Input Voltage 100-125 VAC Max Output Current Total 30A (de-rated to 24A) Max Output Current Each Outlet 15A (de-rated to 12A) Environmental Operating Temperature 50-122 ºF (10-50 ºC) Relative Humidity 5%-95% Mechanical Weight 17 lb. (7.73 kg) Physical Dimensions (W x D x H) 1.8 x 2.2 x 66 in (4.6 x 5.59 x 167.6 cm) Table A.
Appendices Table A.16: PM20i-20A IPDU and PM20i-L20A IPDU Electrical Specifications Characteristics Specifications Electrical Input Voltage 100-240 VAC Max Output Current Total 20A (de-rated to 16A) Max Output Current Each Outlet 10A (de-rated to 8A) Environmental Operating Temperature 32-122 ºF (0-50 ºC) Relative Humidity 5%-95% Mechanical Weight 17 lb. (7.73 kg) Physical Dimensions (W x D x H) 2.0 x 2.8 x 66 in (5.18 x 7.11 x 167.6 cm) Table A.
72 Cyclades PM IPDU Installer/Administrator/User Guide Table A.18: PM20i-32A IPDU and PM20i-32Au IPDU Specifications Characteristics Specifications Electrical Input Voltage 100-240 VAC Max Output Current Total 32A Max Output Current Each Outlet 10A Environmental Operating Temperature 50-122 ºF (10-50 ºC) Relative Humidity 5%-95% Mechanical Weight 17 lb. (7.73 kg) Physical Dimensions (W x D x H) 2.0 x 2.8 x 66 in (5.18 x 7.11 x 167.
Appendices 73 Appendix B: Safety Instructions Follow the safety precautions in this document when installing and operating the Cyclades PM.
74 Cyclades PM IPDU Installer/Administrator/User Guide Sicherheitsanweisungen Bitte lesen und befolgen Sie diese Sicherheitsrichtlinien um sich und Ihren Cyclades PM IPDU vor Schäden zu bewahren. GEFAHR! Auch nach Öffnung einer der beiden Sicherungen kann das Gerät noch unter Spannung über die Phasen- oder Nullleiterzufuhr stehen. GEFAHR! Alle Ausgänge des Cyclades PM IPDU führen Hochspannung. Bitte die erforderlichen Vorsichtsmaßnahmen einhalten.
Appendices 75 Istruzioni di Sicurezza Vi preghiamo di attenervi alle seguenti direttive per la vostra sicurezza e un sicuro utilizzo dell' Cyclades PM IPDU. PERICOLO! Tutte le prese dell'Cyclades PM IPDU sono sotto alta tensione. Occorre prendere precauzioni. PERICOLO! Per evitare di prendere la scossa, inserire la spina dell'Cyclades PM IPDU nell'appropriata presa a terra. L'alimentatore è equipaggiato con una spina a tre poli per assicurare un corretto collegamento.
76 Cyclades PM IPDU Installer/Administrator/User Guide Instruções de Segurança Leia e siga as diretrizes de segurança abaixo para sua proteção e de seu Cyclades PM. PERIGO! Alta voltagem está presente em todas as tomadas do Cyclades PM IPDU. As devidas precauções devem ser tomadas. PERIGO! Para evitar choques elétricos, conecte o Cyclades PM IPDU a uma tomada devidamente aterrada. O cabo de força possui uma tomada com três pinos para ajudar a garantir que o devido aterramento seja feito.
Appendices 77 Instrucciones de seguridad Lea y siga estas pautas de seguridad para protegerse a usted y a su Cyclades PM. ¡PELIGRO! Todos los enchufes de salida Cyclades PM IPDU tienen alto voltaje. Se deben tomar las precauciones necesarias. ¡PELIGRO! Para ayudar a prevenir descargas eléctricas, conecte el Cyclades PM IPDU en una fuente de energía correctamente puesta a tierra. El cable eléctrico está equipado de un enchufe del tres conectores para ayudar a asegurar la puesta a tierra apropiadamente.
78 Cyclades PM IPDU Installer/Administrator/User Guide Instructions de sécurités Lisez et suivez les instructions de sécurité pour votre protection et celle ce le Cyclades PM IPDU DANGER! Toutes les prises de l'Cyclades PM produisent une tension électrique élévée. Prenez les précautions d'usage. DANGER! Pour aider à éviter tout choc électrique, branchez l'Cyclades PM IPDU à une source électrique correctement liée à la terre.
Appendices 79 Appendix C: Circuit Breakers The PM IPDU circuit breakers are designed to shut the power off to some or all of the PM IPDU outlets in case the rated current is exceeded. The circuit breaker mechanism for each PM IPDU model is explained the in the following sections.
80 Cyclades PM IPDU Installer/Administrator/User Guide Figure C.1: PM10-L30A IPDU Circuit Breakers PM10i-L30A IPDU The PM10i-L30A IPDU has two 15-amp circuit breakers. The first circuit breaker controls outlets 6 through 10; the second controls outlets 1 through 5. In the event that the total current flow to outlets 6 through 10 exceeds 15 amps due to equipment connected to these outlets, the first circuit breaker will trip causing outlets 6 through 10 to shutdown.
Appendices 81 will trip causing outlets 6 through 10 to shutdown. This does not affect outlets 1 through 5, which are controlled by the second circuit breaker. As the PM10i-32A has the controller powered from the line side of one of the circuit breakers, the whole unit will be inoperative only if both circuit breakers trip, but the controller will still function. When either circuit breaker trips, only the power outlets of that segment will be affected, and half of the outlets remain operative.
82 Cyclades PM IPDU Installer/Administrator/User Guide When either circuit breaker trips, only the power outlets of that segment will be affected, and half of the outlets remain operative. Figure C.4: PM20i-L30A IPDU, PM20i-32A IPDU and PM20i-32Au IPDU Circuit Breakers PM20i-32A IPDU and PM20i-32Au IPDU The PM20i-32A IPDU and the PM20i-32Au IPDU have two 16-amp circuit breakers. The first circuit breaker controls outlets 11 through 20; the second controls outlets 1 through 10.
Appendices 83 Circuit Breaker Trip Time Depending on the model, the Cyclades PM IPDU uses either one 10 amp, one 20 amp, two 15 amp, or two 16 amp circuit breakers. The following table shows the circuit breaker trip time for all PM IPDU models. Table C.1: Circuit Breaker Trip Time Current Load Trip Time 200% 5-30 seconds 300% 1.8-10 seconds 400% 0.9-5 seconds 500% 0.5-3.3 seconds 600% 0.38-2.3 seconds 800% 0.2-1.3 seconds 1000% 0.15-0.
84 Cyclades PM IPDU Installer/Administrator/User Guide
85 INDEX Index A PM20i-L30A 82 PM20-L30A 81 AC power 20 adduser 33 command line interface 31 adduser command 24 commands 32 admin configuration default parameters 23 logging in as 22 admin password 25 initial 24 alarm 34 integrated 4 alarms and monitoring 1 restoring the 53 AlterPath PM saving 25, 53 standalone 2, 3 components 7 models 7 console 20, 21 accessing the 21 user interface 31 logging in through the 22 assign command 24, 34 assigning outlets to users 24 console access direct
86 Cyclades PM Installer/Administrator/User Guide deluser command 39 K E Kermit 2, 21 electrical and hardware specifications 63 L equipment required for installation 13 exit command 41 list command 47 local work station 21 lock command 48 F factory_defaults command 41 firmware upgrade 26 logging in 22 loopback connector 25 flash memory 7 M H maximum outlets supported 19 hardware configuration options 2 help command 42 HyperTerminal 2, 21 Minicom 2, 21 modular input power cables 14 mounting
Index overview, PM 1 PM8 7 -15A model 63 P -20A model 64 part numbers 13 passwd command 50 -L20A model 64 PM8i 8, 79 pinouts, In and Out RS-232 serial ports 72 -10A model 64 plugging devices into outlets 20 PM8i-15A model 15 PM10 8 port -15A model 65 -20A model 65 console 21 ports -L20A model 65 In 20, 21, 22 -L30A model 66, 79, 80 Out 3, 4, 19 PM10i 9, 79 power cables -10A model 15, 66 modular input 14 -15A model 16, 67 PM10i-10A 15 -16A model 16, 67 PM10i-15A 16 -20A model 16, 6
88 Cyclades PM Installer/Administrator/User Guide PM8-L20A 64 RJ-45 to RJ-45 7ft.
FCC Warning Statement The Cyclades PM IPDU has been tested and found to comply with the limits for Class A digital devices, pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment.