System information

Appendix A: Advanced Device Configuration 355
How the OnBoard Manages Communications With Devices
1. Log into the OnBoard’s console as an administrator and run the
onbdtemplate utility.
2. Select New from the menu.
3. Enter a template name, such as rsa.new.
The editor brings up a template for a new command template assigning it
the name you specified.
4. Enter the device type in the form “type = device_type.”
Using the syntax supported on the device, perform the following steps to
fill in the commands supported by the service processor. Follow the
instructions in the template you are editing.
Note: Sensors may not be supported. If any command is not supported, leave
it commented out in the template.
5. Enter the login prompt in the form “login_prompt = login_prompt.”
6. Enter the password prompt in the form “pass_prompt =
pass_prompt.”
7. Enter the command prompt in the form “cmd_prompt =
cmd_prompt.”
8. Enter the logout command in the form “logout_cmd = logout_cmd.”
9. Enter the power on command in the form “poweron_cmd =
poweron_cmd.”
10. Enter the power off command in the form “poweroff_cmd =
poweroff_cmd.”
11. Enter the power cycle command in the form “powercycle_cmd =
powercycle_cmd.”
12. Enter the power status command in the form “powerstatus_cmd =
powerstatus_cmd.”
13. Enter the reset command in the form “reset_cmd = reset_cmd.”
14. Enter the sensors command in the form “sensors_cmd =
sensors_cmd.”