System information

Configuring Sensor Alarms
234 AlterPath OnBoard Administrator’s Guide
T To Begin Configuring a Sensor Alarm
Perform this procedure to monitor a sensor on a specific devices and
configure an alarm trigger and a notification to be sent if the specified alarm
trigger occurs. See “OnBoard Notifications” on page 43.
1. Log into the Web Manager as an administrative user and go to Config
Sensor Alarms.
2. Click the “Add new alarm” button.
The add sensor alarm dialog appears.
3. Select a device from the “Device” pull-down menu.
4. Specify the sensor to monitor in the “Sensor” field.
5. Select a condition to trigger the sensor alarm from the “Condition” pull-
down menu.
6. When the condition selected in Step 5 is inside or outside a range, specify
the range in the “Range” fields.
7. Specify a polling interval and choose “minutes” or “hours” from the
“Interval” pull-down menu.
8. Select the desired notification action from the “Action” pull-down menu.
9. Enter a comment, if desired, in the “Comment” field.
10. Go to the appropriate procedure from the following table, depending on
which option is selected from the “Action” menu in Step 8.
Configuring a “Syslog Message” Sensor Alarm
Action
The following figure shows the fields that appear when “Syslog Message” is
selected on the “Action” menu on the Config Sensor Alarms screen that is
shown in Figure 7-28.
To Configure a Syslog Message Sensor Alarm Action Page 235
To Configure an SNMP Trap Sensor Alarm Action Page 236
To Configure a Pager Sensor Alarm Action Page 238
To Configure an Email Sensor Alarm Action Page 240