CyBro-2 conforms to the Electromagnetic Compatibility Directive (89/336/EEC) and Low Voltage
Directive (73/23/EEC) requirements of the following standards:
EN 50081-2: Electromagnetic compatibility - generic emission standard for industrial environment
EN 61000-3-2 +A1 +A2: Electromagnetic compatibility - harmonic current emissions
EN 61000-3-3: Electromagnetic compatibility - voltage fluctuations and flicker
EN 61000-6-2: Electromagnetic compatibility - immunity for industrial environments
EN 61131-2 +A11: Equipment requirements and tests for programmable controllers
General technical specifications
European Union directives (CE)
Power supply requirements for 230V~
Isolation voltage (mains
power supply to SELV)
Effects of improper supply
voltage
Dips and short interruptions
Steady-state r.m.s. input
current
Maximum inrush current
Frequency tolerance
Voltage tolerance
Nominal power supply
The unit should be connected to mains, which is installation category II.
The building installation should have overcurrent protective device with nominal value of 16A or less
Too high supply voltage will cause the built in fuse
to blow up. Too small supply voltage will cause the PLC to trip.
Too small frequency will have no influence on proper functioning.
Improper lead connection will cause no harm. Connecting line
to N terminal and neutral to L terminal is not safety relevant.
interruptions: 95%, 5000ms
voltage dips: 30% (10ms), 60% (100ms)
0.07A at 230V~ under full load condition
3000V~, 1 minute
10A peak at 264V~
-5% +5%
-15% +10%
100-240V~ 50/60Hz 20VA
Descriptopn
ITEM
Requirements for transport
and storage
Operating conditions
Sinusoidal vibrations
temperature: -10..75°C
humidity: 85% rh max. non-condensing
min. atmospheric pressure for transportation: 70kPa
There are no special arrangements to be made regarding
transport and storage as long as CyBro is originally packed.
Description
temperature: 0..50°C
humidity: 85% rh max. non-condensing
0.075mm amplitude 10-57Hz; 1G 57-150Hz
10 sweeps each axis, 1 octave/minute
±4kV contact
±8kV air
30MHz..1GHz, 10V/m, 80% modulation with 1kHz signal
Electrostatic discharge
Radiated electromagnetic
field
Fast transient/burst
Surge
Induced RF current
Installation category
Enclosure protection rating
Pollution degree
power port: 2kV
signal port: 1kV
differential mode: 1kV
common mode: 2kV
power port: 10V 80%
signal port 3V 80%
II
IP20
2
ITEM
23
Common techical specifications