User manual

I/O table
ix0..ix11 Digital inputs.
general error A one or more system errors occured (timeout, program or bus error).
timeout_error Communication failed, no messages are coming from the module.
program_error Internal or configuration error detected, module is not functional.
bus_error Module detected a number of communication errors, but it is still working.
qx0..qx11 Digital outputs.
sys_req Set to send new filter settings to module. Will be reset automatically after
settings are sent.
no_filter Disable default input filtering (5ms) for each particular input (no_filter=12
-> ix2 and ix3 not filtered). Use in critical applications to achieve a minimum
response time.
slow_filter Enable extra input filtering (100ms) for each particular input (slow_filter=14
-> ix1, ix2 and ix3 slow filtering). Useful in a noisy environment.
Technical specifications
Number of i/o points 12 digital inputs
12 digital outputs
IX (digital inputs)
Input type 24V, typ. 7mA, sink or source (PNP or NPN), opto isolated
Debounce filter 0, 5ms, 100ms, software selectable, independent for each input
QX (digital outputs)
Output type relay contacts, normaly open
Load max. 3A/250V~ or 3A/30V=, resistive
Operate/release time max. 10ms
Life time 1x10 operations (0.5A 250V~ 30V=, resistive)
2x10 operations (3A 250V~ 30V=, resistive)
Power consumption 24V 160mA (64mA+8mA*number of active relays)
Galvanic isolation inputs/outputs are galvanic isolated from internal circuit
IEX-2 baud rate 20, 50, 100, 250, 500kbps, auto selectable
Operation temperature 0..50°C, 0..85% rh non-condensing
Dimension 106x90x58mm
Weight 280g
Enclosure IP20
Installation category II
Level of ambient pollution 2